Date |
Text |
2020-10-22 09:39:05 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| NFPA 70 2014 EDITION |
| |
| ENRIQUE QUINONEZ |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6746 |
| [email protected] |
| |
| FROM PREVIOUS REVIEW: |
| |
| 1) CORRECTED. |
| |
| 2) VALUE FOR SIGN TOO LOW. SUBMIT A SIGNED CONTRACT FOR |
| WORK INVOLVED. SEE 2ND REVIEW NOTES. |
| |
| 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF |
| THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, |
| QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS |
| (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE |
| BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION |
| OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT |
| VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, |
| ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT, EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| 2ND REVIEW: |
| |
| 3) UNSIGNED CONTRACT RECEIVED BUT IT INCLUDES A SECOND |
| SIGN, BUT NO PLAN SUBMITTED FOR THE OTHER SIGN FBC 107, |
| SCOPE NOT CLEAR. PERMIT VALUE NOT YET ADJUSTED. |
| |
| 4) PREVIOUS PLANS WERE SIGNED AND SEALED BY AN |
| ENGINEER, THE SECOND SUBMISSION DOES NOT INCLUDE THE |
| SEAL AND SIGNATURE. PLANS NEED TO BE SIGNED AND SEALED |
| BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB FBC |
| 107.2.1, 107.3.5; FS 471, 481. |
| |
| ENRIQUE QUINONEZ |
| |