Plan Review Notes For Permit 20081346 |
Permit Number |
20081346 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-09-10 07:59:59 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | | | NO ELECTRIC SHOWN PLEASE SUBMIT SIZE OF BRANCH CIRCUIT | | , AND SHOW GFCI PROTECTION. |
|