Plan Review Notes
Plan Review Notes For Permit 20081298
Permit Number 20081298
Review Stop G
Sequence Number 1
Notes
Date Text
2020-09-24 08:16:521ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20081298
 9/24/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AN LP GAS RISER DRAWING SHOWING THE TYPES
 AND SIZES OF PIPING; TOTAL DEVELOPED LENGTH OF THE
 SYSTEM AND LENGTHS OF BRANCHES TO ALL NEW AND EXISTING
 LP APPLIANCES OR EQUIPMENT; TOTAL BTUH LOAD OF THE
 SYSTEM AND INDIVIDUAL LOADS OF APPLIANCES OR EQUIPMENT;
 LOCATIONS AND TYPES OF SHUTOFF VALVES, LOCATIONS AND
 MAKES AND MODELS OF REGULATORS INCLUDING INLET AND
 OUTLET PRESSURES, LOCATIONS OF UNION, RISERS AND FLEX
 CONNECTORS; AND A LIST OF GAS PIPE SIZING TABLES-
 SECTION 107.2.1 WPB. PLEASE NOTE THE UPDATED GENERAC
 SPECIFICATIONS INDICATE THE A 306,000 FULL BTUH LOAD
 FOR THE 22 KW GENERATOR. PROVIDE UPDATED SPECS AND
 MARKED UP SPECS FOR THE REGULATORS SHOWING THE SELECTED
 MODELS TO BE INSTALLED.
  
 2) SUBMIT A SUB-PERMIT FOR THE INSTALLATION OF THE TANK
 AND THE PIPING- SECTION 105.1 WPB. THE SUBMITTED
 APPLICATIONS BEAR EC LICENCES WHICH ARE NOT VALID FOR
 THE LP TANK INSTALLATION. THE SUB-PERMIT APPLICATION
 SHALL BEAR THE CONTRACTOR'S FDACS LP GAS LICENSE
 NUMBER.
  
 3) PLEASE MARK UP THE SUBMITTED SURVEY TO SHOW THE
 REQUIRED 10 FT. CLEARANCES DISTANCES FROM THE TANK TO
 THE BUILDING, AND ADJACENT PROPERTY LINES- TABLE
 6.3.1.1 NFPA 58. PLEASE SHOW THE PIPING RUN ON THE
 SURVEY FROM THE TANK TO THE GENERATOR.
  
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 500-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE
 BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED)
 IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE
 REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN
 SECTION 5.2.1.1 NFPA 58.
  
 5) PROVIDE LP TANK INSTALLATION DETAILS AS OUTLINED IN
 THE SUBMITTED CONTRACT, AND AS REQUIRED BY NFPA 58:
 A) ENGINEERING FOR ANCHORING THE TANK TO PREVENT
 FLOTATION, COLLAPSE, OR LATERAL MOVEMENT- SECTION
 6.6.1.6. PLEASE INCLUDE A FRONT AND SIDE ELEVATION VIEW
 THAT SHOWS THE BURIAL DEPTH, ANCHORING BASE MATERIAL,
 AND THE TYPES, SIZES, AND NUMBERS OF ANCHORS, CABLES OR
 STRAPS, AND THE TYPE OF PROTECTIVE SLEEVES FOR THE
 CABLES OR STRAPS
 B) SHOW HOW THE TANK WILL BE PROTECTED AGAINST
 CORROSION BY INSTALLATION OF A CATHODIC PROTECTION
 SYSTEM CONSISTING OF A SACRIFICIAL ANODE OR AN
 IMPRESSED CURRENT ANODE PER SECTIONS 5.2.1.11 &
 6.6.6.1(I) NFPA 58. INDICATE THE TYPE OF PROTECTION AND
 HOW IT WILL BE TESTED- SECTION 6.17.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  