2020-09-24 08:16:52 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20081298 |
| 9/24/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE AN LP GAS RISER DRAWING SHOWING THE TYPES |
| AND SIZES OF PIPING; TOTAL DEVELOPED LENGTH OF THE |
| SYSTEM AND LENGTHS OF BRANCHES TO ALL NEW AND EXISTING |
| LP APPLIANCES OR EQUIPMENT; TOTAL BTUH LOAD OF THE |
| SYSTEM AND INDIVIDUAL LOADS OF APPLIANCES OR EQUIPMENT; |
| LOCATIONS AND TYPES OF SHUTOFF VALVES, LOCATIONS AND |
| MAKES AND MODELS OF REGULATORS INCLUDING INLET AND |
| OUTLET PRESSURES, LOCATIONS OF UNION, RISERS AND FLEX |
| CONNECTORS; AND A LIST OF GAS PIPE SIZING TABLES- |
| SECTION 107.2.1 WPB. PLEASE NOTE THE UPDATED GENERAC |
| SPECIFICATIONS INDICATE THE A 306,000 FULL BTUH LOAD |
| FOR THE 22 KW GENERATOR. PROVIDE UPDATED SPECS AND |
| MARKED UP SPECS FOR THE REGULATORS SHOWING THE SELECTED |
| MODELS TO BE INSTALLED. |
| |
| 2) SUBMIT A SUB-PERMIT FOR THE INSTALLATION OF THE TANK |
| AND THE PIPING- SECTION 105.1 WPB. THE SUBMITTED |
| APPLICATIONS BEAR EC LICENCES WHICH ARE NOT VALID FOR |
| THE LP TANK INSTALLATION. THE SUB-PERMIT APPLICATION |
| SHALL BEAR THE CONTRACTOR'S FDACS LP GAS LICENSE |
| NUMBER. |
| |
| 3) PLEASE MARK UP THE SUBMITTED SURVEY TO SHOW THE |
| REQUIRED 10 FT. CLEARANCES DISTANCES FROM THE TANK TO |
| THE BUILDING, AND ADJACENT PROPERTY LINES- TABLE |
| 6.3.1.1 NFPA 58. PLEASE SHOW THE PIPING RUN ON THE |
| SURVEY FROM THE TANK TO THE GENERATOR. |
| |
| 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| 500-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE |
| BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED) |
| IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE |
| REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN |
| SECTION 5.2.1.1 NFPA 58. |
| |
| 5) PROVIDE LP TANK INSTALLATION DETAILS AS OUTLINED IN |
| THE SUBMITTED CONTRACT, AND AS REQUIRED BY NFPA 58: |
| A) ENGINEERING FOR ANCHORING THE TANK TO PREVENT |
| FLOTATION, COLLAPSE, OR LATERAL MOVEMENT- SECTION |
| 6.6.1.6. PLEASE INCLUDE A FRONT AND SIDE ELEVATION VIEW |
| THAT SHOWS THE BURIAL DEPTH, ANCHORING BASE MATERIAL, |
| AND THE TYPES, SIZES, AND NUMBERS OF ANCHORS, CABLES OR |
| STRAPS, AND THE TYPE OF PROTECTIVE SLEEVES FOR THE |
| CABLES OR STRAPS |
| B) SHOW HOW THE TANK WILL BE PROTECTED AGAINST |
| CORROSION BY INSTALLATION OF A CATHODIC PROTECTION |
| SYSTEM CONSISTING OF A SACRIFICIAL ANODE OR AN |
| IMPRESSED CURRENT ANODE PER SECTIONS 5.2.1.11 & |
| 6.6.6.1(I) NFPA 58. INDICATE THE TYPE OF PROTECTION AND |
| HOW IT WILL BE TESTED- SECTION 6.17.1 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |