2020-09-02 15:45:561ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20081288
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ON THE GAS RISER DIAGRAM SHEET: NOTE 4 INDICATES
 ?PIPE SIZED BASED ON THE LONGEST LENGTH METHOD? BUT IT
 DOES NOT GIVE US THE LONGEST LENGTH TO THE MOST REMOTE
 APPLIANCE FROM THE GAS METER. PLEASE PROVIDE THE LENGTH
 AS WE CANNOT SIZE THIS SYSTEM UNTIL WE HAVE THAT
 NUMBER. FBC FG 402.4.2
  
 2) PIPE SECTION (A) IS SUPPLYING THE EXISTING GAS
 SYSTEM AND THE NEW GAS LINE TO THE GENERATOR. WE MUST
 HAVE THE LONGEST LENGTH TO THE MOST REMOTE APPLIANCE
 BEFORE WE CAN SIZE THIS SECTION OF PIPE TO DETERMINE
 THAT IS CAN SUPPLY THE NEW LOAD. FBC FG 402.4.2
  
 3) THE NEW REGULATOR TO THE GENERATOR HAS A NOTE
 INDICATING SECTION 410.10, PLEASE CHECK THESE NUMBERS
 AS THERE IS NO SECTION 410.10 IN THE 2017 FBC FG.
  
 4) THE NEW GAS LINE TO THE NEW GENERATOR HAS A
 MEASUREMENT OF 20?. WE DO NOT USE THIS NUMBER TO SIZE
 THE PIPE SUPPLYING GAS TO THE GENERATOR UNLESS IT IS IN
 FACT THE DISTANCE FOR THE MOST REMOTE APPLIANCE FROM
 THE GAS METER. AS THERE ARE NO MEASUREMENTS INDICATED
 ON THE GAS RISER FOR THE EXISTING PIPING SYSTEM I HAVE
 NO WAY OF KNOWING HOW TO SIZE THIS GAS SYSTEM. PLEASE
 SHOW LENGTHS TO THE EXISTING GAS APPLIANCES SO WE CAN
 COME UP WITH THE DISTANCE TO THE MOST REMOTE APPLIANCE
 FROM THE GAS METER. FBC FS 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  