Plan Review Notes
Plan Review Notes For Permit 20081283
Permit Number 20081283
Review Stop SIGNATURE
Sequence Number 2
Notes
Date Text
2021-03-29 14:56:53CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. SAME COMMENTS AS FIRST REVIEW.
  
 1) PER THE WPB AMENDMENTS TO THE FBC, ELECTRICAL PLAN
 IS REQUIRED TO BEAR THE NAME AND BE SIGNED BY THE
 PERSON RESPONSIBLE FOR THE DESIGN. THIS PERSON MUST BE
 A LICENSED DESIGN PROFESSIONAL OR THE ELECTRICAL
 CONTRACTOR QUALIFIER. PROVIDE CORRECTION. WPB FBC
 107.1, 107.2; FS 471, 481
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved