Plan Review Notes
Plan Review Notes For Permit 20081228
Permit Number 20081228
Review Stop P
Sequence Number 1
Notes
Date Text
2020-10-16 13:18:401ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20081228
 10/16/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1.0: SHOW THE CLEAR FLOOR SPACE DIAGRAMS AND
 DIMENSIONS FOR THE DRINKING FOUNTAIN AND BREAKROOM
 SINK- SECTIONS 305.3 & 305.5 FBC ACC.
  
 2) A1.0: SHOW THE DEPTH DIMENSION OF THE DF ALCOVE-
 SECTION 305.7 FBC ACC.
  
 3) A3.4: PROVIDE DETAILS SHOWING THE DF KNEE AND TOE
 CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS- SECTION
 602.2 FBC ACC.
  
 4) A3.4: PLEASE PROVIDE THE FOLLOWING MISSING
 ACCESSIBILITY DETAILS.
  
 A) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORY-
 SECTION 606.2.
 B) SHOW THE COMPLETE ARC OF THE DOOR TO VERIFY IT WILL
 NOT SWING INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY-
 SECTION 602.2.3 FBC ACC.
 C) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOOR- SECTION 604.4.
 D) HEIGHTS OF THE FRONT RIM OF THE LAVATORIES FROM THE
 FINISHED FLOORS- SECTION 606.3
 E) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 306.
 H) GRAB BAR LENGTHS, SPACINGS FROM ADJACENT WALLS, AND
 MOUNTING HEIGHTS FROM THE FINISHED FLOOR TO THE TOP OF
 THE GRIPPING SURFACES- SECTION 604.5 & 609.4
 J) THE CENTERLINES OF THE TOILET PAPER DISPENSERS
 MEASURED FROM THE FRONT EDGES OF THE WATER CLOSETS-
 SECTION 604.7.
 L) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3.
  
 5) INDICATE THE TYPE AND DIMENSIONS OF WALL BACKING
 MATERIAL TO BE INSTALLED AT THE MOP SINK- SECTION 310.3
 FBC P AND SECTION 1210.2.2 FBC B.
  
 6) P0.0: PROVIDE THE EFFICIENCY RATING OF THE WATER
 HEATER AND SUBMIT A MANUFACTURER'S SPEC SHEET TO VERIFY
 COMPLIANCE WITH TABLE C404.2 FBC EC.
  
 7) P0.0: PROVIDE A DEVICE SCHEDULE SHOWING MAKES,
 MODELS AND LISTINGS FOR THE WATER HAMMER ARRESTORS,
 MIXING VALVES, BACKFLOW PREVENTERS, AND TRAP PRIMERS-
 SECTIONS 604.9, 607.1.2, 608.1, & 1002.4.1.1 FBC P.
  
 8) P2.0: SHOW THE LOCATION OF THE REQUIRED CLEANOUT AT
 THE JUNCTION OF THE BUILDING DRAIN AND BUILDING SEWER
 LINE- SECTION 708.1.3 FBC P.
  
 9) P2.0: PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1
 WPB. SHOW THE WIDTH OF THE REPAIR; THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED; THE
 SIZE, SPACING, AND EMBEDMENT DEPTH OF THE DOWELS; AND
 THE ANCHORING MATERIAL FOR THE DOWELS. THE REPAIR SHALL
 ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AND THE
 REQUIRED VAPOR BARRIER OVER WELL-COMPACTED SOIL. PLEASE
 NOTE A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION APPROVAL.
  
 10) P4.0: THE LOCATIONS OF THE TRAP PRIMERS FOR THE
 FLOOR DRAINS IN THE RESTROOMS ARE NOT CLEARLY
 IDENTIFIED- SECTION 1002.4.1.1 FBC P.
  
 11) SUBMIT A PLUMBING SUB-PERMIT APPLICATION AS
 REQUIRED BY SECTION 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  