Plan Review Notes For Permit 20081223 |
Permit Number |
20081223 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-11-14 10:17:32 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | 1) FBC B 107.2.1, THE SUBMITTEDPLANS INDICATE A FOOTING | | DETAIL FOR PAVERS AND/OR A FOOTING DETAIL FOR A SCREEN | | ENCLOSURE. PLEASE PROVIDE (ON PLAN) THE LOCATION AND | | TYPE OF FOOTINGS TO BE USED. | | (SCREEN ENCLOSURE WILL REQUIRE A SEPARATE PERMIT). | | 2) FBC R 4501.17.1 - 4501.17.3, IDENTIFY THE LOCATION & | | TYPE OF CHILD BARRIERS TO BE USED AS PER CODE | | REQUIREMENTS: (PERIMETER YARD FENCE, SCREEN ENCLOSURE, | | CHILD BARRIER, WINDOW/DOOR ALARMS). | | |
|