2020-09-15 13:26:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. DOMESTIC WATER RISER DIAGRAM ON P0.1 SHOWS ? INCH
 COLD WATER ROUTED OVERHEAD TO ICEMAKER. P3.1 PLAN VIEW
 SHOWS IT GOING TO A BEVERAGE DISPENSER. PER WPB FBC
 107.2.1, CLARIFY.
  
 2. DOMESTIC WATER RISER DIAGRAM ON P0.1 SHOWS ? INCH
 COLD WATER TO RO SYSTEM BUT NO PROVISION IS MADE IN THE
 SANITARY FOR WASTE DISPOSAL. PROVIDE A TRAPPED AND
 VENTED DEDICATED WASTE RECEPTOR TO RECEIVE THE
 DISCHARGE OF THE RO SYSTEM. PROVIDE AN INDIRECT WASTE
 WITH AN AIR GAP. COMPLY WITH FBC PL 802.2, 802.2.1 AND
 802.3.
  
 3. SANITARY RISER DIAGRAM ON P0.1 SHOWS A 2 INCH WASTE
 AND VENT FOR SK-1 FIXTURE. P2.1 PLAN VIEW SHOWS A FLOOR
 DRAIN CONNECTED TO SANITARY AS WELL AS SK-1. PER WPB
 FBC 107.2.1, CLARIFY AND ADVISE AS TO THE PURPOSE OF
 THE FLOOR DRAIN. PLEASE NOTE:
 A. PER FBC PL 412.2, FLOOR DRAINS SHALL HAVE REMOVABLE
 STRAINERS. THE FLOOR DRAIN SHALL BE CONSTRUCTED SO THAT
 THE DRAIN IS CAPABLE OF BEING CLEANED. ACCESS SHALL BE
 PROVIDED TO THE DRAIN INLET. READY ACCESS SHALL BE
 PROVIDED TO FLOOR DRAINS.
 B. PER FBC PL 802.3, FOR OTHER THAN HUB DRAINS THAT
 RECEIVE ONLY CLEAR-WATER WASTE AND STANDPIPES, A
 REMOVABLE STRAINER OR BASKET SHALL COVER THE OUTLET OF
 WASTE RECEPTORS. WASTE RECEPTORS SHALL NOT BE INSTALLED
 IN CONCEALED SPACES. WASTE RECEPTORS SHALL NOT BE
 INSTALLED IN PLENUMS, CRAWL SPACES, ATTICS,
 INTERSTITIAL SPACES ABOVE CEILINGS AND BELOW FLOORS.
 READY ACCESS SHALL BE PROVIDED TO WASTE RECEPTORS
 C. PER FBC PL 802.2.1, AN AIR GAP BETWEEN THE INDIRECT
 WASTE PIPE AND THE FLOOD LEVEL RIM OF THE WASTE
 RECEPTOR SHALL BE NOT LESS THAN TWICE THE EFFECTIVE
 OPENING OF THE INDIRECT WASTE PIPE.
  
 4. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION/INSTALLATION MANUAL FOR THE INSINKERATOR
 FAUCET AND THE RO SYSTEM.
 5. PER FBC PL 604.9, PROVIDE WATER HAMMER ARRESTOR
 CONFORMING TO ASSE 1010 AT THE DISHWASHER AND ICE MAKER
 LINES.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20081205 1641 WORTHINGTON RD # 410
  
  
  