2020-09-15 13:26:50 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| |
| 1ST REVIEW |
| PLUMBING COMMENTS: DENIED |
| |
| 1. DOMESTIC WATER RISER DIAGRAM ON P0.1 SHOWS ? INCH |
| COLD WATER ROUTED OVERHEAD TO ICEMAKER. P3.1 PLAN VIEW |
| SHOWS IT GOING TO A BEVERAGE DISPENSER. PER WPB FBC |
| 107.2.1, CLARIFY. |
| |
| 2. DOMESTIC WATER RISER DIAGRAM ON P0.1 SHOWS ? INCH |
| COLD WATER TO RO SYSTEM BUT NO PROVISION IS MADE IN THE |
| SANITARY FOR WASTE DISPOSAL. PROVIDE A TRAPPED AND |
| VENTED DEDICATED WASTE RECEPTOR TO RECEIVE THE |
| DISCHARGE OF THE RO SYSTEM. PROVIDE AN INDIRECT WASTE |
| WITH AN AIR GAP. COMPLY WITH FBC PL 802.2, 802.2.1 AND |
| 802.3. |
| |
| 3. SANITARY RISER DIAGRAM ON P0.1 SHOWS A 2 INCH WASTE |
| AND VENT FOR SK-1 FIXTURE. P2.1 PLAN VIEW SHOWS A FLOOR |
| DRAIN CONNECTED TO SANITARY AS WELL AS SK-1. PER WPB |
| FBC 107.2.1, CLARIFY AND ADVISE AS TO THE PURPOSE OF |
| THE FLOOR DRAIN. PLEASE NOTE: |
| A. PER FBC PL 412.2, FLOOR DRAINS SHALL HAVE REMOVABLE |
| STRAINERS. THE FLOOR DRAIN SHALL BE CONSTRUCTED SO THAT |
| THE DRAIN IS CAPABLE OF BEING CLEANED. ACCESS SHALL BE |
| PROVIDED TO THE DRAIN INLET. READY ACCESS SHALL BE |
| PROVIDED TO FLOOR DRAINS. |
| B. PER FBC PL 802.3, FOR OTHER THAN HUB DRAINS THAT |
| RECEIVE ONLY CLEAR-WATER WASTE AND STANDPIPES, A |
| REMOVABLE STRAINER OR BASKET SHALL COVER THE OUTLET OF |
| WASTE RECEPTORS. WASTE RECEPTORS SHALL NOT BE INSTALLED |
| IN CONCEALED SPACES. WASTE RECEPTORS SHALL NOT BE |
| INSTALLED IN PLENUMS, CRAWL SPACES, ATTICS, |
| INTERSTITIAL SPACES ABOVE CEILINGS AND BELOW FLOORS. |
| READY ACCESS SHALL BE PROVIDED TO WASTE RECEPTORS |
| C. PER FBC PL 802.2.1, AN AIR GAP BETWEEN THE INDIRECT |
| WASTE PIPE AND THE FLOOD LEVEL RIM OF THE WASTE |
| RECEPTOR SHALL BE NOT LESS THAN TWICE THE EFFECTIVE |
| OPENING OF THE INDIRECT WASTE PIPE. |
| |
| 4. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S |
| SPECIFICATION/INSTALLATION MANUAL FOR THE INSINKERATOR |
| FAUCET AND THE RO SYSTEM. |
| 5. PER FBC PL 604.9, PROVIDE WATER HAMMER ARRESTOR |
| CONFORMING TO ASSE 1010 AT THE DISHWASHER AND ICE MAKER |
| LINES. |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS |
| REQUIRED BY FAC AND FS. |
| ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| |
| |
| |