Plan Review Notes
Plan Review Notes For Permit 20081196
Permit Number 20081196
Review Stop B
Sequence Number 2
Notes
Date Text
2020-11-02 11:23:52PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE A SITE PLAN WITH LOCATION OF PROPOSED
 WINDOWS.
 COMPLETE.
  
  
 2. PROVIDE SITE SPECIFIC DESIGN WIND LOADS.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 PROVIDE A WINDOW SCHEDULE WITH DESIGN PRESSURES FOR
 EACH OPENING OR PLACE THE DESIGN PRESSURES NEXT TO EACH
 OPENING ON THE SITE PLAN.
  
 N EW COMMENT:
  
 3. BATHROOM WINDOW FL14911 IS A NON-IMPACT RATED
 WINDOW.
 OPENING PROTECTION REQUIRED.
 PROVIDE A SCHEDULE FOR OPENING PROTECTION.
 107.2 CONSTRUCTION DOCUMENTS.
  
 4. PROVIDE PRODUCT APPROVALS FOR SHUTTER TO BE
 INSTALLED.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
  