Plan Review Notes
Plan Review Notes For Permit 20081174
Permit Number 20081174
Review Stop B
Sequence Number 1
Notes
Date Text
2020-08-27 11:27:45PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PRODUCT APPROVALS (FL10545-R4) THAT WERE
 SUBMITTED FOR THE ROLL UP GARAGE DOORS HAVE A MAXIMUM
 DESIGN PRESSURE OF +/- 45 PSF. THE (2) LOADING BERTH
 DOORS ARE 12'-8" X16'-0" AND THE (4) GARAGE DOORS ARE
 (2) AT 10'-8" X 9'-0 AND (2) AT 10'-8" X 9'-6". THE
 WORST CASE CLADDING LOADS FROM THE WIND TUNNEL TESTING
 REPORT HAS +90, -180 PSF FOR THE DOORS AT LEVEL P1.
 PLEASE CLARIFY HOW THESE DOORS WILL MEET THE REQUIRED
 WIND PRESSURES.