Plan Review Notes For Permit 20081174 |
Permit Number |
20081174 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-08-27 11:27:45 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE PRODUCT APPROVALS (FL10545-R4) THAT WERE | | SUBMITTED FOR THE ROLL UP GARAGE DOORS HAVE A MAXIMUM | | DESIGN PRESSURE OF +/- 45 PSF. THE (2) LOADING BERTH | | DOORS ARE 12'-8" X16'-0" AND THE (4) GARAGE DOORS ARE | | (2) AT 10'-8" X 9'-0 AND (2) AT 10'-8" X 9'-6". THE | | WORST CASE CLADDING LOADS FROM THE WIND TUNNEL TESTING | | REPORT HAS +90, -180 PSF FOR THE DOORS AT LEVEL P1. | | PLEASE CLARIFY HOW THESE DOORS WILL MEET THE REQUIRED | | WIND PRESSURES. |
|