Plan Review Notes
Plan Review Notes For Permit 20081118
Permit Number 20081118
Review Stop G
Sequence Number 1
Notes
Date Text
2020-09-25 15:10:101ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT-20081118
 9/25/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE RISER DRAWING SHALL BE REVISED TO SHOW THE
 COMPLETE GAS PIPING SYSTEM INCLUDING THE PIPING TO ALL
 NEW AND EXISTING APPLIANCES. ACCORDING TO WPB BUILDING
 DEPT. RECORDS, AN EXTERIOR GAS-FIRED TANKLESS WATER
 HEATER AND NEW RANGE WERE INSTALLED UNDER PERMIT
 19081423. THE REVISED DRAWING SHALL SHOW:
  
 A) THE BRANCH PIPE RUNS TO ALL APPLIANCES AND EQUIPMENT
 INCLUDING THE TYPES AND SIZES OF GAS PIPING- G2412.3 &
 G2414.1 FBC RES.
  
 A) TOTAL BTUH OF THE SYSTEM, AND THE INDIVIDUAL
 APPLIANCE AND EQUIPMENT LOADS- SECTIONS G2412.3,
 G2412.4, & G2413.2.
  
 B) BRANCH LENGTH PIPE CONNECTIONS AT THE METER, THE
 INDIVIDUAL BRANCH LENGTHS AND THE TOTAL DEVELOPED
 LENGTH OF THE SYSTEM- SECTIONS G2413.4.1 & G2413.4.2.
  
 C) MAKE AND MODEL OF THE NEW REGULATOR AND INLET AND
 OUTLET PRESSURES- SECTION G2421.1 & 2421.2. PLEASE SHOW
 THE LOCATIONS OF EXISTING REGULATORS AND OUTLET
 PRESSURES. G2413.4(1) THROUGH G2413.4(8) FBC RES
 PRESSURES.
  
 D) LIST THE PIPE SIZING TABLES USED FOR THE SYSTEM-
 REFER TO TABLES G2413.4(1) THROUGH G2413.4(8) FBC RES.
  
 2) SUBMIT MARKED UP OR HIGHLIGHTED REGULATOR SPECS
 SHOWING THE SELECTED MODEL, THE INLET AND OUTLET SIZE
 AND PRESSURES, AND ORIFICE SIZE. PLEASE NOTE THAT THE
 SPECS FOR THE REGULATOR AND NEW POOL HEATER SHALL BE
 ONSITE AT TIME OF INSPECTION- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  