Plan Review Notes For Permit 20081094 |
Permit Number |
20081094 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-09-08 11:51:49 | PLAN REVIEW / ELECTRICAL | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | NEC 2014 | | | | 1ST REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. SMOKE DETECTORS MISSING INSIDE BEDROOM #2, OUTSIDE | | BEDROOM #2, OUTSIDE BEDROOM #3 AND OUTSIDE MASTER | | BEDROOM PER R314.3. | | R314.3 LOCATION. | | SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING | | LOCATIONS: | | 1.IN EACH SLEEPING ROOM. | | 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE | | VICINITY OF THE BEDROOMS. | | | | 2. PROVIDE LUMINAIRE AND OUTLET FOR MECHANICAL | | EQUIPMENT IN ATTIC PER M1305.1.3.1. | | PROVIDE GFCI PROTECTED OUTLET AND SWITCH CONTROLLED | | LIGHT FOR SERVICING EACH AHU LOCATED IN AN ATTIC. FBC | | MECHANICAL CODE M306.3.1 | | |
|