Plan Review Notes
Plan Review Notes For Permit 20081013
Permit Number 20081013
Review Stop G
Sequence Number 1
Notes
Date Text
2020-08-31 14:41:161ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20081013
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE INDICATE IF THIS IS A NEW SERVICE OR EXISTING
 SERVICE SUPPLYING OTHER GAS APPLIANCES. FBC FS 107.2.1
  
 2) GAS RISER DIAGRAM SPECS 10? OF PE PIPING FOR THE NEW
 GENERATOR. THE OVERHEAD SURVEY MAP INDICATES THE GAS
 METER WILL BE ON THE OTHER SIDE OF THE HOUSE FROM WHERE
 THE NEW GENERATOR WILL BE LOCATED. PLEASE CORRECT THIS
 AND SHOW BOTH DRAWINGS TO BE CONSISTENT. FBC FS 107.2.1
  
 3) PLEASE PROVIDE THE GENERATOR SPECS. FBC FS 107.2.1
  
 4) PLEASE PROVIDE SPEC SHEET FOR THE GENERATOR PAD. FBC
 FS 107.2.1
  
 5) PROVIDE THE REGULATOR SPECS. PLEASE MARK WHICH
 REGULATOR AND SPRING USED FOR THIS INSTALLATION. FBC FS
 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  