Plan Review Notes
Plan Review Notes For Permit 20080987
Permit Number 20080987
Review Stop E
Sequence Number 2
Notes
Date Text
2021-04-23 10:31:41CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: APPROVED, SEE COMMENTS BELOW.
  
 1) SPACING OF RECEPTACLES NEEDS TO COMPLY WITH NEC
 210.52(A). FLOOR RECEPTACLES NEED TO BE LOCATED WITHIN
 18 INCHES OF THE WALL TO COUNT FOR THE REQUIRED NUMBER
 OF RECEPTACLES. NEC 210.52(A)
  
 CORRECTED
  
 2) EXISTING RISER DIAGRAM SHOWS #2/0 FEEDERS FROM 200
 AMPS BREAKERS TO ELECTRICAL PANELS. SIZE #2/0 IS ONLY
 GOOD FOR 175 AMPS AND BECAUSE THIS AMPACITY MATCHES A
 175 AMPS STANDARD SIZE BREAKER YOU ARE NOT ALLOWED TO
 JUMP TO THE NEXT STANDARD SIZE AND A #3/0 CU IS
 REQUIRED. PLEASE DOUBLE CHECK WHAT SIZE IS CURRENTLY
 EXISTING TO MAKE SURE INSTALLATION COMPLIES WITH NEC
 240.4 (B)(2).
  
 RISER SHOWS 2 SETS OF #2/0
  
  
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  
  