Plan Review Notes
Plan Review Notes For Permit 20080982
Permit Number 20080982
Review Stop G
Sequence Number 1
Notes
Date Text
2020-09-10 14:20:551ST REVIEW FBC-2017 RES.
 PERMIT- 20080982
 9/10/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS ISOMETRIC DRAWING:
 A) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE INTERIOR
 PIPING RUN- SECTION G2413.4.1 & G2413.4.2 FBC RES, AND
 THE TOTAL BTUH LOAD OF THE ENTIRE SYSTEM- SECTION
 G2413.2 FBC RES.
  
 B) THE SPECS SUBMITTED FOR THE GENERATOR UNDER
 PERMIT-20070263 INDICATE 327,000 BTUH AT FULL LOAD-
 PLEASE CORRECT- SECTION 107.2.1 WPB.
  
 C) INDICATE THE PIPE SIZING TABLE ON THE DRAWING- SEE
 TABLES G2413.4(1)- G2413.4(8) FBC RES.
  
 D) SHOW THE LOCATIONS OF THE FLEX CONNECTOR, SHUTOFF
 VALVE FOR THE GAS SUPPLY TO THE GENERATOR, AND THE
 REQUIRED PIPE UNION AT THE REGULATOR- SECTIONS G2420.4,
 G2420.5, AND G2421.2(7).
  
 E) SUBMIT MANUFACTURER'S SPECS FOR THE B42 SERIES
 REGULATOR WITH MARKUPS ON THE COPY TO INDICATE THE
 MODEL NUMBER, INLET PRESSURE, ORIFICE AND SPRING SIZE
 OF THE SELECTED REGULATOR- SECTION G2421.1 & G2421.2.
  
 F) SUBMIT MANUFACTURER'S SPECS FOR THE GENERATOR FLEX
 CONNECTOR THAT INDICATE MANUFACTURER AND MODEL, LISTING
 STANDARDS, AND INSTALLATION GUIDELINES- SECTION
 G2415.1.
  
 G) INDICATE A TRACER WIRE WILL BE INSTALLED ADJACENT TO
 THE UG PE PIPING- SECTION G2415.17.3.
  
 H) INDICATE HOW THE PE PIPING RISERS WILL CONNECT TO
 THE METALLIC PIPING PER SECTIONS G2415.17.1 &
 G2415.17.2. PLEASE NOTE THAT SPECS FOR ANODELESS RISERS
 AND PE/METALLIC PIPE CONNECTORS SHALL BE LISTED AND
 LABELED.
  
 2) SUBMIT INSTALLATION GUIDELINES FROM GENERAC TO
 VERIFY THE LOCATION CLEARANCES FOR THE GENERATOR AS
 SHOWN ON THE SURVEY. PLEASE PROVIDE A CLEARER COPY OF
 THE MARKED-UP SURVEY SHOWING THE GENERATOR DISTANCES TO
 THE BUILDING, OPERABLE OPENINGS INTO THE BUILDING, AND
 THE ADJACENT PROPERTY LINES- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  