2020-09-10 14:20:55 | 1ST REVIEW FBC-2017 RES. |
| PERMIT- 20080982 |
| 9/10/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS ISOMETRIC DRAWING: |
| A) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE INTERIOR |
| PIPING RUN- SECTION G2413.4.1 & G2413.4.2 FBC RES, AND |
| THE TOTAL BTUH LOAD OF THE ENTIRE SYSTEM- SECTION |
| G2413.2 FBC RES. |
| |
| B) THE SPECS SUBMITTED FOR THE GENERATOR UNDER |
| PERMIT-20070263 INDICATE 327,000 BTUH AT FULL LOAD- |
| PLEASE CORRECT- SECTION 107.2.1 WPB. |
| |
| C) INDICATE THE PIPE SIZING TABLE ON THE DRAWING- SEE |
| TABLES G2413.4(1)- G2413.4(8) FBC RES. |
| |
| D) SHOW THE LOCATIONS OF THE FLEX CONNECTOR, SHUTOFF |
| VALVE FOR THE GAS SUPPLY TO THE GENERATOR, AND THE |
| REQUIRED PIPE UNION AT THE REGULATOR- SECTIONS G2420.4, |
| G2420.5, AND G2421.2(7). |
| |
| E) SUBMIT MANUFACTURER'S SPECS FOR THE B42 SERIES |
| REGULATOR WITH MARKUPS ON THE COPY TO INDICATE THE |
| MODEL NUMBER, INLET PRESSURE, ORIFICE AND SPRING SIZE |
| OF THE SELECTED REGULATOR- SECTION G2421.1 & G2421.2. |
| |
| F) SUBMIT MANUFACTURER'S SPECS FOR THE GENERATOR FLEX |
| CONNECTOR THAT INDICATE MANUFACTURER AND MODEL, LISTING |
| STANDARDS, AND INSTALLATION GUIDELINES- SECTION |
| G2415.1. |
| |
| G) INDICATE A TRACER WIRE WILL BE INSTALLED ADJACENT TO |
| THE UG PE PIPING- SECTION G2415.17.3. |
| |
| H) INDICATE HOW THE PE PIPING RISERS WILL CONNECT TO |
| THE METALLIC PIPING PER SECTIONS G2415.17.1 & |
| G2415.17.2. PLEASE NOTE THAT SPECS FOR ANODELESS RISERS |
| AND PE/METALLIC PIPE CONNECTORS SHALL BE LISTED AND |
| LABELED. |
| |
| 2) SUBMIT INSTALLATION GUIDELINES FROM GENERAC TO |
| VERIFY THE LOCATION CLEARANCES FOR THE GENERATOR AS |
| SHOWN ON THE SURVEY. PLEASE PROVIDE A CLEARER COPY OF |
| THE MARKED-UP SURVEY SHOWING THE GENERATOR DISTANCES TO |
| THE BUILDING, OPERABLE OPENINGS INTO THE BUILDING, AND |
| THE ADJACENT PROPERTY LINES- SECTION 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |