Plan Review Notes
Plan Review Notes For Permit 20080940
Permit Number 20080940
Review Stop G
Sequence Number 1
Notes
Date Text
2020-09-03 13:49:15CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
  
 GAS COMMENTS: DENIED
  
 1. A REVIEW OF PUBLIC RECORDS DOES NOT SHOW THAT ANY
 GAS PERMIT AND PLAN(S) HAVE BEEN APPLIED FOR THE
 EXISTING GAS POOL HEATER NOTED ON THE GAS PLAN, NOR FOR
 THE GAS WATER HEATER AND THE GAS COOKTOP INDICATED IN
 MASTER PERMIT FOR GENERATOR #20070805. IF SYSTEM IS NOT
 TO COMPLIANT WITH 2017 FBC RES/FBC FG, IT MAY REQUIRE
 TO BE BROUGHT UP TO CODE AT OWNER EXPENSE WITH A NEW
 PERMIT AND REVIEW. THIS MAY REQUIRE INSPECTIONS AND
 TESTING TO ASCERTAIN THE COMPLIANCE AND INTEGRITY OF
 THE SYSTEM(S) AS DETERMINED BY THE INSPECTOR.
 RECORDS OF ORIGINAL PERMIT #95008841 INDICATES ALL
 ELECTRIC APPLIANCES.
 PER WPB FBC 107.2.1, SUBMIT A COMPLETE GAS RISER
 SHOWING ALL PIPE SIZES, TYPE OF PIPE, THE DEVELOPED
 LENGTH TO THE FURTHEST GAS OUTLET OF 2PSI SYSTEM AND
 SYSTEMS DOWNSTREAM OF MP REGULATORS, THE BTU LOAD OF
 EACH APPLIANCE, THE PSI OF THE SYSTEM(S), THE TYPE OF
 GAS AND THE TOTAL BTU LOAD ON THE SYSTEM. PROVIDE TABLE
 FOR SYSTEMS DOWNSTREAM OF MP REGULATORS.
  
 2. PER WPB FBC 107.2.1, CONFIRM THAT THE FIREPLACE HAS
 NOT BEEN CONVERTED TO NATURAL GAS .IF IT HAS THEN
 INCLUDE IN THE RISER AND CALCULATIONS.
  
 3. RE: 2PSI SYSTEM; DISTANCE FROM METER TO FURTHEST
 APPLIANCE (GENERATOR) EXCEEDS 100 FEET; IT IS
 APPROXIMATELY 115 FEET PER THE GAS RISER DIAGRAM.
 SUBMITTED FBC FG TABLE 402.4(18) INDICATES 100 FEET.
 PER WPB FBC 107.2.1, REVISE AND RESUBMIT.
  
 4. RISER DIAGRAM INDICATES 3/4 INCH CSST. PER WPB FBC
 107.2.1 PROVIDE CORRECT TUBE SIZE (EHD) TO CORRESPOND
 WITH SUBMITTED FBC FG TABLE 402.4(18).
  
 5. GAS PIPING PLAN SHOWS EXISTING POOL HEATER AT 400
 MBTU. PLEASE NOTE THAT ALTHOUGH THERE DOES NOT APPEAR
 TO BE A GAS PERMIT APPLIED FOR, PERMIT #96002653 FOR A
 POOL INDICATES A NATURAL GAS FIRED POOL HEATER AT 75
 MBTU. THIS NEEDS TO BE CLARIFIED.
  
 6. SUBMIT A HOUSE PLAN SHOWING THE FOLLOWING:
 A.THE LOCATION OF THE TYPE OF WATER HEATER(TANK TYPE OR
 TANK-LESS) AND THE LOCATION AND DISTANCE OF ANY
 OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER
 HEATER OR THE VENTING OF SAID WATER HEATER. THE
 LOCATION OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS.
 B. ALL OTHER GAS APPLIANCES AS WELL AS LOCATION OF
 METER.
  
 PLEASE NOTE, THE HOUSE PLAN CAN BE HAND DRAWN. REFER TO
 WPB FBC 107.2.1. A PLAN OF RECORD IS AVAILABLE FROM THE
 WPB BUILDING DEPARTMENT BY CONTACTING CRAIG MCPHERSON
 AT 561-805-6684; EMAIL [email protected].
  
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
  
 AN ORIGINAL SIGNED PLAN(S) SHALL BE SUBMITTED PRIOR TO
 PERMIT ISSUE. CALL 561-805-6724 OR EMAIL [email protected]
 FOR ADDITIONAL INFORMATION.
  
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20080940 8453 EGRET MEADOW LN
  
  