2020-09-03 13:49:15 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 54 = NATIONAL FUEL GAS CODE |
| FS = FLORIDA STATUTES |
| |
| |
| 1ST REVIEW |
| |
| GAS COMMENTS: DENIED |
| |
| 1. A REVIEW OF PUBLIC RECORDS DOES NOT SHOW THAT ANY |
| GAS PERMIT AND PLAN(S) HAVE BEEN APPLIED FOR THE |
| EXISTING GAS POOL HEATER NOTED ON THE GAS PLAN, NOR FOR |
| THE GAS WATER HEATER AND THE GAS COOKTOP INDICATED IN |
| MASTER PERMIT FOR GENERATOR #20070805. IF SYSTEM IS NOT |
| TO COMPLIANT WITH 2017 FBC RES/FBC FG, IT MAY REQUIRE |
| TO BE BROUGHT UP TO CODE AT OWNER EXPENSE WITH A NEW |
| PERMIT AND REVIEW. THIS MAY REQUIRE INSPECTIONS AND |
| TESTING TO ASCERTAIN THE COMPLIANCE AND INTEGRITY OF |
| THE SYSTEM(S) AS DETERMINED BY THE INSPECTOR. |
| RECORDS OF ORIGINAL PERMIT #95008841 INDICATES ALL |
| ELECTRIC APPLIANCES. |
| PER WPB FBC 107.2.1, SUBMIT A COMPLETE GAS RISER |
| SHOWING ALL PIPE SIZES, TYPE OF PIPE, THE DEVELOPED |
| LENGTH TO THE FURTHEST GAS OUTLET OF 2PSI SYSTEM AND |
| SYSTEMS DOWNSTREAM OF MP REGULATORS, THE BTU LOAD OF |
| EACH APPLIANCE, THE PSI OF THE SYSTEM(S), THE TYPE OF |
| GAS AND THE TOTAL BTU LOAD ON THE SYSTEM. PROVIDE TABLE |
| FOR SYSTEMS DOWNSTREAM OF MP REGULATORS. |
| |
| 2. PER WPB FBC 107.2.1, CONFIRM THAT THE FIREPLACE HAS |
| NOT BEEN CONVERTED TO NATURAL GAS .IF IT HAS THEN |
| INCLUDE IN THE RISER AND CALCULATIONS. |
| |
| 3. RE: 2PSI SYSTEM; DISTANCE FROM METER TO FURTHEST |
| APPLIANCE (GENERATOR) EXCEEDS 100 FEET; IT IS |
| APPROXIMATELY 115 FEET PER THE GAS RISER DIAGRAM. |
| SUBMITTED FBC FG TABLE 402.4(18) INDICATES 100 FEET. |
| PER WPB FBC 107.2.1, REVISE AND RESUBMIT. |
| |
| 4. RISER DIAGRAM INDICATES 3/4 INCH CSST. PER WPB FBC |
| 107.2.1 PROVIDE CORRECT TUBE SIZE (EHD) TO CORRESPOND |
| WITH SUBMITTED FBC FG TABLE 402.4(18). |
| |
| 5. GAS PIPING PLAN SHOWS EXISTING POOL HEATER AT 400 |
| MBTU. PLEASE NOTE THAT ALTHOUGH THERE DOES NOT APPEAR |
| TO BE A GAS PERMIT APPLIED FOR, PERMIT #96002653 FOR A |
| POOL INDICATES A NATURAL GAS FIRED POOL HEATER AT 75 |
| MBTU. THIS NEEDS TO BE CLARIFIED. |
| |
| 6. SUBMIT A HOUSE PLAN SHOWING THE FOLLOWING: |
| A.THE LOCATION OF THE TYPE OF WATER HEATER(TANK TYPE OR |
| TANK-LESS) AND THE LOCATION AND DISTANCE OF ANY |
| OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER |
| HEATER OR THE VENTING OF SAID WATER HEATER. THE |
| LOCATION OF THE WATER HEATER SHALL COMPLY WITH THE |
| MANUFACTURER'S INSTALLATION INSTRUCTIONS. |
| B. ALL OTHER GAS APPLIANCES AS WELL AS LOCATION OF |
| METER. |
| |
| PLEASE NOTE, THE HOUSE PLAN CAN BE HAND DRAWN. REFER TO |
| WPB FBC 107.2.1. A PLAN OF RECORD IS AVAILABLE FROM THE |
| WPB BUILDING DEPARTMENT BY CONTACTING CRAIG MCPHERSON |
| AT 561-805-6684; EMAIL [email protected]. |
| |
| |
| A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS |
| FROM THE FIRST REVIEW. |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS |
| REQUIRED BY FAC AND FS. |
| |
| AN ORIGINAL SIGNED PLAN(S) SHALL BE SUBMITTED PRIOR TO |
| PERMIT ISSUE. CALL 561-805-6724 OR EMAIL [email protected] |
| FOR ADDITIONAL INFORMATION. |
| |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-246-0882 MOBILE |
| |
| 20080940 8453 EGRET MEADOW LN |
| |
| |