Plan Review Notes
Plan Review Notes For Permit 20080939
Permit Number 20080939
Review Stop G
Sequence Number 1
Notes
Date Text
2020-09-03 15:38:21FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
  
 GENERAL COMMENTS:
 REFER TO CLOSED GAS PERMIT #01040190 FOR EXISTING GAS
 SYSTEM AND APPLIANCES
 REFER TO MP #20070807 FOR LOCATION OF GAS METER AND NEW
 GENERATOR IN RELATION TO THE RESIDENCE.
 REFER TO MP #20070807 FOR MANUFACTURER?S
 SPECIFICATION/USER MANUAL FOR THE GENERATOR.
  
  
 GAS COMMENTS: DENIED
  
 1. THE RISER DIAGRAM IS VERY LIGHT AND HARD TO READ.
 PER WPB FBC 107.2.1, PROVIDE A CLEAR AND LEGIBLE RISER
 DIAGRAM.
  
 2. RISER DIAGRAM INDICATES 3/4 INCH PE FOR UNDERGROUND
 WITH 12 INCH WC. FBC RES TABLE G2413.4(7) / FBC FG
 TABLE 402.4(21) FOR THAT SYSTEM REQUIRES 1-1/2 INCH
 SIZE BASED UPON CLOSED GAS PERMIT #01040190 LESS THAN 2
 PSI LONGEST LENGTH OF 115 FEET. SUBMITTED TABLE FROM
 NFPA 54-44, TABLE 6.2(V) IS FOR 2PSI PE.
  
 3. PROVIDE APPROPRIATE TABLES INCLUDING ABOVE GROUND
 PIPING, AND CLARIFY PRESSURE SYSTEMS. WILL THERE BE A
 NEW UTILITIES REGULATOR PROVIDING 2 PSI? PROVIDE DETAIL
 SIZING/MATERIAL/TABLE AT THE METER/REGULATOR FOR
 MANIFOLD FROM REGULATOR TO NEW BRANCH FOR NEW
 GENERATOR, IF LESS THAN 2 PSI,THAT SIZE SHALL BE 2 INCH
 PER FBC RES TABLE G2413.4(1)/ FBC FG 402.4(2). IF
 SYSTEM IS TO BE 2PSI THAT SIZE WILL BE DETERMINED BY
 FBC RES TABLE G2413.4(2)/ FBC FG 402.4(5); SHOW
 LOCATION OF ALL MP REGULATORS.
  
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS
 REQUIRED BY FAC AND FS.
  
 AN ORIGINAL SIGNED PLAN(S) SHALL BE SUBMITTED PRIOR TO
 PERMIT ISSUE. CALL 561-805-6724 OR EMAIL [email protected]
 FOR ADDITIONAL INFORMATION.
  
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20080939 10688 GRANDE BLVD
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved