2020-08-21 13:32:11 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20080898 |
| 8/21/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE 3/4" PE PIPE IS UNDERSIZED FOR THE TOTAL BTUH |
| LOAD OF 395,700 OR THE 355,700 LOAD OF THE TWH AND NEW |
| RANGE AT 17 FT. DEVELOPED LENGTH- SEE SUBMITTED TABLE |
| 402.4(21) FBC FG, OR RELEVANT TABLE G2413.4(7) FBC RES. |
| A MINIMUM 1" PE PIPE IS REQUIRED. |
| 2) PROVIDE THE PIPE SIZING TABLE FOR THE 3/4" |
| GALVANIZED PIPE AND LIST BOTH THE PE AND METALLIC PIPE |
| SIZING TABLES ON THE RISER DRAWING- SECTION G2413.4 FBC |
| RES. |
| |
| 3) PLEASE INDICATE HOW THE NEW GAS RANGE WILL BE |
| VENTED- TABLE 1507.4 AND SECTION G2447.1 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |