Plan Review Notes
Plan Review Notes For Permit 20080881
Permit Number 20080881
Review Stop E
Sequence Number 1
Notes
Date Text
2020-09-03 16:12:52ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
  
 1) PANEL SCHEDULE STATES PANEL IS 60A? WITH OVER 100A
 LOAD
  
 2) AIC CALCULATION REQUIRED FOR THE SERVICE AND PANEL.
 110.9, 110.10, LABELS REQUIRED PER 110.24
  
 3) SEVERAL LOADS IN PANEL SHOW NO LO0ADS FOR
 CALCULATION.
  
 4) RISER DOES NOT SHOW ANY WIRE SIZES. 120 AMP? SHOW
 WIRE SIZES FOR SUBFEEDER TO PANEL. 215.5
  
 5) 40% IS FOR A RESIDENTIAL CALCULATION AS STATED IN
 YOUR LOAD SUMMARY. 215.5
  
 6) ALL 120VOLT OUTLETS IN KITCHEN AREA TO BE GFCI
 PROTECTED 210.8
  
 7) PLAN SHOWS TWO WATER HEATERS??