Plan Review Notes
Plan Review Notes For Permit 20080785
Permit Number 20080785
Review Stop P
Sequence Number 1
Notes
Date Text
2020-08-24 10:14:0908/24/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT PER THE WPB AMENDMENTS TO THE FBC SEC. 109.3
 BUILDING PERMIT VALUATIONS.
  
 2. ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. SIGNED AND SEALED DRAWINGS NEED
 TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER
 OR ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. IT
 APPEARS THE MAIN PERMITTED SET HAVE AN ELECTRONIC
 SIGNATURE, BUT THESE DONE.
 3. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 4. IN SHEET C400 IT SHOWS A STORM LINE MOVED TO A
 DIFFERENT LOCATION PLEASE CLARIFY IF THIS IS PART OF
 THE SCOPE OF WORK OR A REVISION WAS DONE OR WILL BE
 NEEDED PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. IN SHEET C401 IT SHOWS A WATER LINE FOR FIRE AND NOT
 CLEAR IF THIS IS PART OF THE SCOPE OF WORK THAT IS
 GOING TO TAKE PLACE. THIS MAY REQUIRE A REVISION AND
 FURTHER REVIEW BY THE ENGINEERING DEPARTMENT PLEASE
 CLARIFY, THIS FIRE LINE CAN ONLY BE INSTALLED BY A FIR
 PREVENTION AND CONTROL LICENSED CONTRACTOR I, II AND V
 ACCORDING TO 2017 FLORIDA STATUTES 633.102.
  
 6. A GENERAL CONTRACTOR OR AN UNDERGROUND UTILITY AND
 EXCAVATION CONTRACTOR CANNOT INSTALL A SEWER PER THE
 2019 FLORIDA STATUTES TITLE XXXII CHAPTER 489.105(N).
 PLEASE PROVIDE THE PERMITTING DEPARTMENT WITH A VALID
 STATE OF FLORIDA LICENSED CONTRACTOR ALONG WITH AN
 APPLICATION.
  
 FS 489.105 DEFINITIONS.-- AS USED IN THIS PART:
 (1) "BOARD" MEANS THE CONSTRUCTION INDUSTRY LICENSING
 BOARD.
 (2) "DEPARTMENT" MEANS THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION.
 (3) "CONTRACTOR" MEANS THE PERSON WHO IS QUALIFIED FOR,
 AND IS ONLY RESPONSIBLE FOR, THE PROJECT.
  
 (N) "UNDERGROUND UTILITY AND EXCAVATION CONTRACTOR"
 MEANS A CONTRACTOR WHOSE SERVICES ARE LIMITED TO THE
 CONSTRUCTION, INSTALLATION, AND REPAIR, ON PUBLIC OR
 PRIVATE PROPERTY, WHETHER ACCOMPLISHED THROUGH OPEN
 EXCAVATIONS OR THROUGH OTHER MEANS, INCLUDING, BUT NOT
 LIMITED TO, DIRECTIONAL DRILLING, AUGER BORING, JACKING
 AND BORING, TRENCHLESS TECHNOLOGIES, WET AND DRY TAPS,
 GROUTING, AND SLIP LINING, OF MAIN SANITARY SEWER
 COLLECTION SYSTEMS, MAIN WATER DISTRIBUTION SYSTEMS,
 STORM SEWER COLLECTION SYSTEMS, AND THE CONTINUATION OF
 UTILITY LINES FROM THE MAIN SYSTEMS TO A POINT OF
 TERMINATION UP TO AND INCLUDING THE METER LOCATION FOR
 THE INDIVIDUAL OCCUPANCY, SEWER COLLECTION SYSTEMS AT
 PROPERTY LINE ON RESIDENTIAL OR SINGLE-OCCUPANCY
 COMMERCIAL PROPERTIES, OR ON MULTIOCCUPANCY PROPERTIES
 AT MANHOLE OR WYE LATERAL EXTENDED TO AN INVERT
 ELEVATION AS ENGINEERED TO ACCOMMODATE FUTURE BUILDING
 SEWERS, WATER DISTRIBUTION SYSTEMS, OR STORM SEWER
 COLLECTION SYSTEMS AT STORM SEWER STRUCTURES. HOWEVER,
 AN UNDERGROUND UTILITY AND EXCAVATION CONTRACTOR MAY
 INSTALL EMPTY UNDERGROUND CONDUITS IN RIGHTS-OF-WAY,
 EASEMENTS, PLATTED RIGHTS-OF-WAY IN NEW SITE
 DEVELOPMENT, AND SLEEVES FOR PARKING LOT CROSSINGS NO
 SMALLER THAN 2 INCHES IN DIAMETER IF EACH CONDUIT
 SYSTEM INSTALLED IS DESIGNED BY A LICENSED PROFESSIONAL
 ENGINEER OR AN AUTHORIZED EMPLOYEE OF A MUNICIPALITY,
 COUNTY, OR PUBLIC UTILITY AND THE INSTALLATION OF SUCH
 CONDUIT DOES NOT INCLUDE INSTALLATION OF ANY CONDUCTOR
 WIRING OR CONNECTION TO AN ENERGIZED ELECTRICAL SYSTEM.
 AN UNDERGROUND UTILITY AND EXCAVATION CONTRACTOR MAY
 NOT INSTALL PIPING THAT IS AN INTEGRAL PART OF A FIRE
 PROTECTION SYSTEM AS DEFINED IN S. 633.102 BEGINNING AT
 THE POINT WHERE THE PIPING IS USED EXCLUSIVELY FOR SUCH
 SYSTEM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  