2020-08-31 10:26:28 | PLAN REVIEW - ELECTRICAL |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PROVIDE NEW LOAD CALC'S FOR 200 AMP MAIN PANEL THAT |
| INCLUDES THE NEW SUMMER KITCHEN LOADS. |
| PROVIDE ACCURATE LOAD CALCULATIONS INCLUDING ALL LOADS |
| FOR THE SERVICE AS WELL AS THE LOAD CALCULATIONS FOR |
| THE INDIVIDUAL PANELS. NEC 220; FBC RE 3602.2. |
| |
| 2. PROVIDE GROUNDING ELECTRODE SYSTEM OR EQUIPMENT |
| GROUNDING CONDUCTOR TO FOR THE NEW SUMMER KITCHEN SUB |
| PANEL. |
| PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A |
| BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH |
| CIRCUT. NEC 250; FBC RE 3607.3. |
| |
| 3. PROVIDE KITCHEN OUTLET SPACING PER E3901.4. |
| E3901.4.1 WALL COUNTERTOP SPACE. |
| A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL |
| COUNTERTOP SPACE 12 INCHES (305 MM) OR WIDER. |
| RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT |
| ALONG THE WALL LINE IS MORE THAN 24 INCHES (610 MM), |
| MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT |
| SPACE. [210.52(C)(1)] |
| EXCEPTION: RECEPTACLE OUTLETS SHALL NOT BE REQUIRED ON |
| A WALL DIRECTLY BEHIND A RANGE, COUNTER-MOUNTED COOKING |
| UNIT OR SINK IN THE INSTALLATION DESCRIBED IN FIGURE |
| E3901.4.1. [210.52(C)(1) EXCEPTION] |
| |
| E3902.6 KITCHEN RECEPTACLES. |
| 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES |
| THAT SERVE COUNTERTOP SURFACES SHALL HAVE GROUND-FAULT |
| CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. |
| [210.8(A)(6)] |
| |
| |
| |
| |