2021-08-20 17:55:01 | PLAN |
| REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) [THE APPLICATION IS INCORRECT. THIS IS NOT A |
| SUB-PERMIT. GENERATORS REQUIRE A SEPARATE PERMIT. THE |
| FURTHER DESCRIPTION OF WORK STATES NEW CONSTRUCTION OF |
| A 2-STORY SINGLE FAMILY RESIDENCE... THIS SECTION IS |
| INTENEDED TO DESCRIBE THE WORK THAT IS TO BE DONE UNDER |
| THIS PERMIT.SUBMIT A CORRECTED APPLICATION.] (PREVIOUS |
| COMMENT) THIS PERMIT IS FOR THE INSTALLATION OF A |
| RESIDENTIAL GENERATOR. CORRECT THE DESCRIPTION OF WORK |
| ON THE PERMIT APPLICATION. FBC 105 |
| |
| 2) COMPLIED. SUBMIT THE MANUFACTURER'S SPECIFICATIONS |
| AND INSTALLATION INSTRUCTIONS FOR THE GENERATOR. FBC |
| 107.2.1 |
| |
| 3) COMPLIED. PROVIDE DETAILS OF THE GENERATOR PAD AND |
| SPECIFY HOW IT WILL BE ATTACHED TO THE SLAB IN ORDER TO |
| RESIST THE WINDLOADS. FBC-R301 |
| |
| 4) COMPLIED. THIS PROJECT IS LOCATED IN A SPECIAL FLOOD |
| HAZARD. THE GENERATOR IS REQUIRED TO ABOVE THE DFE OF |
| 9' NAVD. FBC-R322 |
| |
| 5) [THIS REQUIREMENT NEEDS TO BE STATED ON THE SITE |
| PLAN OR SHOWN ON THE DRAWINGS.] THE GENERATOR EXHAUST |
| IS REQUIRED TO BE 10' FROM ANY OPENINGS INTO THE |
| BUILDING PER FBC-R303.5.1. |
| |
| 6) AN ELECTRICAL SUB-PERMIT IS REQUIRED FOR THE |
| GENERATOR. FBC AMENDMENTS105 |
| |
| 7) A SEPARATE PERMIT IS REQUIRED FOR GAS. FBC |
| AMENDMENTS105 |