2020-12-22 13:53:18PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS PERMIT IS FOR THE INSTALLATION OF A RESIDENTIAL
 GENERATOR. CORRECT THE DESCRIPTION OF WORK ON THE
 PERMIT APPLICATION. FBC 105
  
 2) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE GENERTATOR. FBC
 107.2.1
  
 3) PROVIDE DETAILS OF THE GENERATOR PAD AND SPECIFY HOW
 IT WILL BE ATTACHED TO THE SLAB IN ORDER TO RESIST THE
 WINDLOADS. FBC-R301
  
 4) THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD.
 THE GENERATOR IS REQUIRED TO ABOVE THE DFE OF 9' NAVD.
 FBC-R322
  
 5) THE GENERATOR EXHAUST IS REQUIRED TO BE 10' FROM ANY
 OPENINGS INTO THE BUIOLDING PER FBC-R303.5.1.