2020-09-22 13:01:24 | SHUTTERS |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| AMENDMENTS |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) PLEASE SHOW THE LOCATION OF THE UNIT WITHIN THE |
| BUILDING FOOT PRINT (AN INTERIOR OR END OF BUILDING |
| UNIT).- NEEDED TO DETERMINE IF THE WINDOWS ARE IN WIND |
| ZONE 4 OR 5. |
| 2) IF AN END UNIT - PLEASE SHOW THE DISTANCE FROM THE |
| CORNER OF THE BUILDING TO THE EDGE OF THE WINDOWS - |
| NEEDED TO DETERMINE IF THE WINDOWS ARE IN WIND ZONE 4 |
| OR 5. |
| 3) WIND DESIGN PRESSURES ARE BASED ON BUILDING HEIGHT - |
| ON THE WIND DESIGN SCHEDULE YOU HAVE CIRCLED THE WIND |
| PRESSURES FOR A 20 FOOT HIGH BUILDING. PLEASE CORRECT |
| THE PRESSURES ON THE "SHUTTER SCHEDULE". |
| 4) PLEASE PROVIDE AN ORIGINAL SIGNED AND SEALED WIND |
| DESIGN PRESSURE SCHEDULE FROM THE ENGINEER. |
| |
| FYI - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO |
| BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. |
| DRAWINGS DO NOT SHOW IN "ADOBE READER" AS |
| DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR |
| ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL |
| SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE |
| ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG |
| WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON |
| FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW |
| REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected] |
| AND ASKING FOR THE FORM. |
| |
| |