Date |
Text |
2020-08-20 15:03:13 | 1ST REVIEW FBC-2017 RES. |
| PERMIT- 20080726 |
| 8/20/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE GAS ISOMETRIC SHOWS THE NEW PIPING TO THE |
| GENERATOR IN COMPLIANCE, HOWEVER THE EXISTING GAS |
| PIPING SHOWN FROM THE NEW REGULATOR AT 12" WC IS |
| UNDERSIZED PER SECTIONS G2413.2, G2413.3, G2413.4, & |
| G2413.4.1 FBC RES. |
| |
| A) USING THE LONGEST LENGTH METHOD, THE TOTAL DEVELOPED |
| LENGTH OF THE SYSTEM IS 142 FT. FROM THE NEW REGULATOR |
| TO THE MOST REMOTE OUTLET (BBQ). THE TOTAL LOAD OF THE |
| SYSTEM IS 610 BTUH. BASED ON TABLE G2413.1 THE PIPE RUN |
| FROM THE REGULATOR TO THE TEE, THE 12 FT. BRANCH LENGTH |
| OF 1-INCH GALVANIZED PIPE RUN UP THE HOUSE WALL (277 |
| BTUH LOAD), AND THE 21 FT. BRANCH LENGTH OF PIPE RUN TO |
| THE POOL HEATER (333 BTUH LOAD) SHALL EACH BE MINIMUM |
| 1-1/4 INCHES. |
| BASED ON TABLE G2413.4(16) THE 70 FT. LENGTH OF 1-INCH |
| CSST (277 BTUH LOAD) SHALL BE SIZED AT A MINIMUM 39 |
| EHD, AND ALL PIPES DOWNSTREAM OF THE CSST WILL HAVE TO |
| INCREASE IN SIZE ACCORDING TO THE TABLES. PLEASE SUBMIT |
| A CORRECT ISOMETRIC DRAWING. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS |
| |