Plan Review Notes
Plan Review Notes For Permit 20080656
Permit Number 20080656
Review Stop B
Sequence Number 1
Notes
Date Text
2020-08-26 10:46:53PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 1) FBC B 107, PROVIDE THE DETAILS FOR COLUMNS C-23 AND
 C-26 AS THE COLUMN SCHEDULE ON PAGE S-1 DOES NOT
 INCLUDE THESE COLUMNS.
 2) FBC B 107, PROVIDE ALL CONNECTION DETAILS FOR BEAMS
 COLUMNS AND FOOTINGS.
 3) FBC B 3301.1, PROVIDE THE DETAILS FOR THE SAFEGUARDS
 DURING CONSTRUCTION, INCLUDING THE TEMPORARY SUPPORT
 SYSTEM METHOD (SHORING).