2020-09-24 08:23:34 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20080620 |
| |
| CODES IN EFFECT: |
| |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET A-1 INDICATES A NEW ADDITION TO THE EXISTING |
| HOUSE, SHEET M.1 DOES NOT SHOW HOW THIS NEW ADDITION IS |
| TO BE CONDITIONED. PLEASE A MECHANICAL SHEET SHOWING |
| THE MECHANICAL SYSTEM FOR THIS NEW ADDITION. FBC FS |
| 107.2.1 |
| |
| 2) PLEASE PROVIDE AN ENERGY ANALYSIS OF THE NEW |
| ADDITION TO THE EXISTING HOUSE. FBC EC 101.5.1.1.2 |
| |
| 3) PLEASE PROVIDE A MANUAL J FOR THE NEW ADDITION TO |
| THE EXISTING HOUSE. FBC EC R403.7 |
| |
| 4) PLEASE PROVIDE A NOTE ON THE DRAWING INDICATING THAT |
| THE AHU IN THE ATTIC MUST MEET SECTION R4.3.3.6 OF THE |
| FBC EC. |
| |
| |
| THIS PROJECT HAS THE PLANS FOR PERMIT#20080654 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |