Plan Review Notes
Plan Review Notes For Permit 20080654
Permit Number 20080654
Review Stop G
Sequence Number 1
Notes
Date Text
2020-09-24 11:23:5609/24/20 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. PLEASE PROVIDE MANUFACTURES SPECIFICATION FOR
 TANK-LESS TO VERIFY BTU AND COMPLIANCE, IF ITS HAS
 CONDENSATE IT WILL NEED TO DRAIN 1' AWAY FROM THE
 STRUCTURE PER THE 2017 FBC SEC. R318.5.
  
 3. THE CITY RECORD HAS A DIFFERENT BTU LOAD FOR THE
 EXISTING GENERATOR AS IT NEEDS TO BE CALCULATED ON THE
 NEW SYSTEM BEFORE AN EVALUATION. PLEASE SUBMIT THE
 MANUFACTURE'S SPECIFICATION OR VERIFY WITH WHAT IS
 INSTALLED PER THE 2017 FBC RES. SEC. G2413.
  
 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR (CLOTHES
 DRYERS) PER THE 2017 FBC RES. SEC. G2407.1 AND G2439.4.
  
 5. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL NEW GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1.
  
 6. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2017
 FBC RES. SEC. G2413.2 AND G2404.3.
  
 7. THE SIZING TABLE USED IN THE DESIGN FOR THE GAS
 SYSTEM IS NOT CLEAR FOR THE CORRECT TABLE NUMBER IN THE
 DESIGN OF THIS SYSTEM PER THE WPB AMENDMENTS TO FBC
 SEC.107.2.1.
  
 8. THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM ON THE ISOMETRIC AND
 LEGEND TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED.
 IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO
 ENSURE A SAFE OPERATING SYSTEM. 2017 FBC RES. SECS.
 G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. NOTE THE
 ASSUMED LOAD IS INCORRECT.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS PER THE 2017 FBC RES. SEC. G2421.1.
  
 10. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF
 REGULATOR 1? OF EITHER SIDE PER THE 2017 FBC RES. SEC
 G2421.2.
  
 11. PLEASE SHOW AND OR LABEL THE SHUTOFF VALVE,
 REGULATOR, AND DRIP LEG ON GAS ISOMERIC PER THE 2017
 FBC RES. SEC. G2401.1.3.
  
 12. PLEASE SHOW THE LOCATION AND DISTANCE OF ANY
 OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER
 HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 HTTPS://CODES.ICCSAFE.ORG/CATEGORY/FLORIDA?YEAR%5B%5D=C
 URRENT+ADOPTION&PAGE=1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  