Plan Review Notes
Plan Review Notes For Permit 20080641
Permit Number 20080641
Review Stop B
Sequence Number 1
Notes
Date Text
2020-09-08 14:11:05WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20080641
 ADD: 917 N. FLAGLER DR.
 CONT: THE HOME DEPOT
 TEL: 954-271-1405
 E-MAIL: ANGELIQUE@[email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 08/2020
 ACTION: DENIED
  
 1) THE SUBMITTED FLOOR PLAN AND SCHEDULE DOES NOT
 INDICATE WHO THE DESIGNER IS? CERTIFICATION BY
 CONTRACTOR.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DRAWN THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN. FOR EACH TRADE THE CONTRACTOR
 RESPONSIBLE FOR THE DESIGN UNDER THE TRADE LICENSED IN
 MUST PRINT THEIR NAME, SIGN THEIR NAME AND LICENSE
 NUMBER.
  
 2) THE SUBMITTED FLOOR PLAN/ SCHEDULE INDICATES THE
 REQUIRED PRESSURES BUT DOES NOT PROVIDE THE DESIGN
 CRITERIA WHERE THESE PRESSURES WERE DERIVED FROM?
 A SUBMITTED SEPARATE WIND DESIGN SCHEDULE LABELED ASCE
 7-16 LIST WIND DESIGN CRITERIA BUT NO CHART. WITH OUR
 CHARTS ASCE 7-10 FOR BUILDINGS LESS THAN 60 FEET TALL
 THE LISTED NEGATIVE PRESSURES ARE APPROXIMATELY 6.0 PSF
 LOW. THE SLIDING GLASS DOOR ELEVATION INDICATES AT 10
 FEET, PLEASE REMEMBER POSITIVE PRESSURES ARE TAKEN FORM
 GRADE TO THE CENTER OF THE OPENING, NEGATIVE PRESSURES
 ARE ALWAYS TAKEN FROM THE MEAN ROOF HEIGHT.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 2.2. RISK CATEGORY.
  
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 2.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 3) THE SUBMITTED SGD NOA 19.1126.03-PAGE 10/26 THE
 LIMITING FACTOR FOR THIS OPENING IS THE SILL HEIGHT,
 SILL HEIGHT IS NOT IDENTIFIED.
 64 SQ. FT. OPENING. ZONE 5 -34.0 X 1.70 = -57.8 VASD.
 PROVIDE WHICH SILL HEIGHT WILL BE INSTALLED TO MAKE
 THIS PRESSURE.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  