Date |
Text |
2021-02-08 12:16:41 | 01/26/21 4TH PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED |
| CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 105.1. |
| |
| 2. THE TDH CALCULATION DOES NOT SHOW THE HEATER, IT |
| MUST INCLUDE ALL THE SYSTEM COMPONENTS INCLUDING |
| SUCTION AND RETURN PIPING, FITTINGS, VALVES, HEATER, |
| FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS EXCEPT |
| THE PUMP. |
| |
| 3. IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS |
| SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS |
| IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE |
| TDH CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2013 SECS. |
| 4.4.9, 4.4.9.1. |
| |
| 4. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL |
| HEATER, FOR THE CARTRIDGE FILTER, AND THE PUMP PER THE |
| WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| |
| 5. THE POOL HEATER SHALL HAVE A MINIMUM THERMAL |
| EFFICIENCY OF 82% PER THE 2017 FBC-ENERGY SEC. |
| R403.10.4. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |