Date |
Text |
2020-10-01 10:38:11 | 010/01/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED |
| CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 105.1. |
| |
| 2. SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE |
| MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM |
| ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN |
| DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER |
| ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 |
| EDITION ADDRESSES THE FLOW RATE IN GALLONS PER MINUTE |
| (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE |
| DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE |
| SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH |
| CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS |
| INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES, |
| HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS |
| EXCEPT THE PUMP. |
| |
| 3. SUBMIT TWO LEGIBLE COPIES OF THE POOL PUMP CURVE. |
| IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC |
| TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS |
| NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH |
| CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2013 SECS. |
| 4.4.9, 4.4.9.1. |
| |
| 4. HEATED SWIMMING POOLS AND INGROUND PERMANENTLY |
| INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT |
| COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR |
| OTHER MEANS PROVEN TO REDUCE HEAT LOSS PER THE 2017 |
| FBC- ENERGY- SEC. R 403.10.3. |
| |
| 5. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE POOL |
| HEATER, FOR THE CARTRIDGE FILTER AND THE PUMP PER THE |
| WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| |
| 6. THE POOL HEATER SHALL HAVE A MINIMUM THERMAL |
| EFFICIENCY OF 82% PER THE 2017 FBC-ENERGY SEC. |
| R403.10.4. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |