2020-08-12 10:59:54 | RESIDENTIAL (R3) MECHANICAL REVIEW COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | 1- FLOOR PLAN SHOWS AN 8" RETURN AIR DUCT. THE RETURN | | AIR DUCT SIZE SHOWN ON THE FLOOR PLAN NEEDS TO BE AT | | LEAST 10" AS REQUIRED BY SEC. M1602.3 EXCEPTION #1. | | REVISE AS REQUIRED. | | | | 2- PROVIDE THE NAME AND SIGNATURE OF THE PERSON | | RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1 | | CITY AMENDMENTS. | | | | 3- THE MECHANICAL WORK WAS NOT INCLUDED IN THE MASTER. | | PLEASE COMPLETE THE ATTACHED REVISION FORM AND INCLUDE | | THE ADDITIONAL VALUE FOR THE MECHANICAL WORK. REVISION | | FEES WILL BE ADJUSTED ACCORDINGLY. SEC. 109.3 CITY | | AMENDMENTS. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|