2020-09-18 15:00:48PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) UNDER DESIGN PARAMETERS ON SHEET T1, THE NOTE STATES
 THIS IS A TWO STORY DWELLING. THE PLANS ARE FOR A
 SINGLE STORY DWELLING. PLEASE CORRECT. CITY AMENDMENTS
 FBC 107.2.1
  
 2) THE WALL SECTION ON SHEET D1 SPECIFIES A 6:12 SLOPE
 ROOF. THE ROOF PLAN ON A4 AND THE ELEVATIONS ON A3
 SPECIFY A 5:12 SLOPE ROOF. PLEASE COORDINATE. CITY
 AMENDMENTS FBC 107.2.1
  
 3) THE SHOWER DETAIL ON D1 IS FOR A SHOWER WITH A CURB
 AND THE PLANS ON A2 SHOW A RECESSED SLAB SHOWER. PLEASE
 COORDINATE. CITY AMENDMENTS FBC 107.2.1
  
 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES. THESE ITEMS CAN BE
 DEFERRED IF REQUESTED, HOWEVER, THE DOCUMENTS MUST BE
 SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT
 BEFORE THEY CAN BE INSTALLED. ONLY ONE SET IS REQUIRED
 TO BE UPLOADED FOR ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 5) FBC ENERGY CONSERVATION R101.5 COMPLIANCE.
 RESIDENTIAL BUILDINGS SHALL MEET THE PROVISIONS OF
 FLORIDA BUILDING CODE, ENERGY CONSERVATION RESIDENTIAL
 PROVISIONS. SUBMIT PERMIT DOCUMENTS AND FORMS TO SHOW
 THAT THE PROPOSED RESIDENTIAL STRUCTURE COMPLIES WITH
 THE ENERGY CODE. FBC ENERGY CONSERVATION
  
 6) ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO
 HAVE THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO
 HAVE THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15
  
 7) BASED ON THE LATEST ICC VALUATION TABLES, THIS
 PROJECT HAS A VALUATION OF $112,785.00. I HAVE ADJUSTED
 THE STATED VALUATION FOR THIS PROJECT ACCORDINGLY. FBC
 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.