2020-08-21 15:34:49 | 1ST REVIEW FBC-2017 RES. |
| PERMIT-20080541 |
| 8/21/2020 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE PLUMBING RISER DRAWINGS FOR THE ALTERATIONS |
| LISTED BELOW AS REQUIRED BY SECTION 107.3.5.3 WPB |
| AMENDMENTS TO THE FBC-17: |
| A) RELOCATED SINK AND DISHWASHER IN THE KITCHEN. |
| B) REPLACED SHOWER AND NEW AND RELOCATED LAVATORIES IN |
| THE MASTER BATH. |
| |
| 2) CONCERNING THE RELOCATED SHOWER DRAIN IN THE MASTER |
| BATH AND THE NEW SHOWER DRAIN IN THE GUEST BATH PLEASE |
| NOTE THAT THE HORIZONTAL DISTANCE FROM THE CENTERLINE |
| OF THE NEW SHOWER DRAIN OUTLET TO THE CENTERLINE OF THE |
| INLET OF THE EXISTING TRAP SHALL NOT EXCEED 30? ? |
| SECTION P3201.6 FBC RES. |
| |
| 3) PROVIDE A SHOWER PLAN DETAIL PER SECTION P2709.1 & |
| P2709.2. |
| |
| 4) PLEASE NOTE THAT THE A BACKFLOW PREVENTER IS |
| REQUIRED FOR THE SUPPLY LINE TO THE ICE MAKER- P2902.1, |
| AND WATER HAMMER ARRESTORS ARE REQUIRED FOR THE SUPPLY |
| LINES TO THE ICE MAKER AND THE DISHWASHER- SECTION |
| P2903.5. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |