2020-10-06 08:09:27PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ANCHOR SPACING TABLE IN THE CORRUGATED PANEL
 SCHEDULE ON PAGE 2 OF 10 ON THE PRODUCT APPROVAL FOR
 THE CLEAR PANELS HAS THE SPANS AND PRESSURES FOR 13"
 SPACING. I DO NOT SEE ANYTHING THAT ALLOWS HIGHER
 PRESSURES FOR CLOSER ANCHOR SPACING. BASED ON THE TABLE
 THE PANELS WITH THE 108" SPAN ARE ONLY GOOD FOR 35 PSF
 AND THE PANELS SPANNING 128" ARE ONLY GOOD FOR 30 PSF.
 THESE PRESSURES ARE TOO LOW FOR THESE OPENINGS. FBC
 107.2.1 & FBC-R301.2.1.2
  
 PER YOUR INSTALLATION SCHEDULE OPENINGS #9 AND 10 HAVE
 A PANEL SPAN 116" AND OPENING #27 HAS A PANEL SPAN OF
 128". THE TABLE FOR THE CLEAR CORRUGATED PANELS ON PAGE
 2 OF 10 OF THE PRODUCT APPROVAL HAS PRESSURES OF LESS
 THAN THE 50 PSF THAT IS REQUIRED PER YOUR INSTALLATION
 SCHEDULE. SINCE THESE DO NOT MEET THE REQUIRED
 PRESSURES THEY CAN NOT BE APPROVED FOR THIS PROJECT.
 OPENINGS #7 WITH THE 91" SPAN AND #18 WITH THE 82" SPAN
 BOTH HAVE PRESSURES OF MORE THAN 50 PSF AND ARE
 ACCEPTABLE. THE ANCHOR SPACING IS 13" O.C. PER THE
 TABLE ON PAGE 2 OF 10. YOU CAN NOT USE ANY OTHER
 SPACING WITHOUT SIGNED AND SEALED CALCULATIONS FROM AN
 ENGINEER.
  
 2) PLEASE PROVIDE A RESPONSE LETTER EXPLAINING HOW
 THESE COMMENTS WILL BE ADDRESSED.