2020-10-06 08:09:27 | PLAN |
| REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE ANCHOR SPACING TABLE IN THE CORRUGATED PANEL |
| SCHEDULE ON PAGE 2 OF 10 ON THE PRODUCT APPROVAL FOR |
| THE CLEAR PANELS HAS THE SPANS AND PRESSURES FOR 13" |
| SPACING. I DO NOT SEE ANYTHING THAT ALLOWS HIGHER |
| PRESSURES FOR CLOSER ANCHOR SPACING. BASED ON THE TABLE |
| THE PANELS WITH THE 108" SPAN ARE ONLY GOOD FOR 35 PSF |
| AND THE PANELS SPANNING 128" ARE ONLY GOOD FOR 30 PSF. |
| THESE PRESSURES ARE TOO LOW FOR THESE OPENINGS. FBC |
| 107.2.1 & FBC-R301.2.1.2 |
| |
| PER YOUR INSTALLATION SCHEDULE OPENINGS #9 AND 10 HAVE |
| A PANEL SPAN 116" AND OPENING #27 HAS A PANEL SPAN OF |
| 128". THE TABLE FOR THE CLEAR CORRUGATED PANELS ON PAGE |
| 2 OF 10 OF THE PRODUCT APPROVAL HAS PRESSURES OF LESS |
| THAN THE 50 PSF THAT IS REQUIRED PER YOUR INSTALLATION |
| SCHEDULE. SINCE THESE DO NOT MEET THE REQUIRED |
| PRESSURES THEY CAN NOT BE APPROVED FOR THIS PROJECT. |
| OPENINGS #7 WITH THE 91" SPAN AND #18 WITH THE 82" SPAN |
| BOTH HAVE PRESSURES OF MORE THAN 50 PSF AND ARE |
| ACCEPTABLE. THE ANCHOR SPACING IS 13" O.C. PER THE |
| TABLE ON PAGE 2 OF 10. YOU CAN NOT USE ANY OTHER |
| SPACING WITHOUT SIGNED AND SEALED CALCULATIONS FROM AN |
| ENGINEER. |
| |
| 2) PLEASE PROVIDE A RESPONSE LETTER EXPLAINING HOW |
| THESE COMMENTS WILL BE ADDRESSED. |