Plan Review Notes For Permit 20080536 |
Permit Number |
20080536 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-09-28 11:24:34 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE ANCHOR SPACING TABLE IN THE CORRUGATED PANEL | | SCHEDULE ON PAGE 2 OF 10 ON THE PRODUCT APPROVAL FOR | | THE CLEAR PANELS HAS THE SPANS AND PRESSURES FOR 13" | | SPACING. I DO NOT SEE ANYTHING THAT ALLOWS HIGHER | | PRESSURES FOR CLOSER ANCHOR SPACING. BASED ON THE TABLE | | THE PANELS WITH THE 108" SPAN ARE ONLY GOOD FOR 35 PSF | | AND THE PANELS SPANNING 128" ARE ONLY GOOD FOR 30 PSF. | | THESE PRESSURES ARE TOO LOW FOR THESE OPENINGS. FBC | | 107.2.1 & FBC-R301.2.1.2 | | | | |
|