2020-09-28 11:24:34PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ANCHOR SPACING TABLE IN THE CORRUGATED PANEL
 SCHEDULE ON PAGE 2 OF 10 ON THE PRODUCT APPROVAL FOR
 THE CLEAR PANELS HAS THE SPANS AND PRESSURES FOR 13"
 SPACING. I DO NOT SEE ANYTHING THAT ALLOWS HIGHER
 PRESSURES FOR CLOSER ANCHOR SPACING. BASED ON THE TABLE
 THE PANELS WITH THE 108" SPAN ARE ONLY GOOD FOR 35 PSF
 AND THE PANELS SPANNING 128" ARE ONLY GOOD FOR 30 PSF.
 THESE PRESSURES ARE TOO LOW FOR THESE OPENINGS. FBC
 107.2.1 & FBC-R301.2.1.2
  
  