2020-09-11 15:09:16PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ANCHOR SPACING TABLE IN THE PRODUCT APPROVAL FOR
 THE CLEAR PANELS IS ILLEGIBLE. I WAS NOT ABLE TO VERIFY
 THE ANCHOR SPACING. SUBMIT LEGIBLE PRODUCT APPROVAL.
 FBC 107.2.1
  
 2) THE ANCHOR SPACING IN THE SCHEDULE FOR THE ROLL UP
 DOOR OF 9" IS NOT CORRECT FOR 50 PSF, A 118" SPAN,
 TRAPPED MOUNT AND 5/16 TAPCONS. THE ANCHOR SPACING
 TABLE ON SHEET 17 HAS 5.5" FOR THIS INSTALLATION. THE
 9" ANCHOR SPACING IS FOR 3/8" DIAMETER KWIK BOLT 3
 ANCHORS IN THE TABLE ON SHEET 16. FBC 107.2.1