Plan Review Notes For Permit 20080536 |
Permit Number |
20080536 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-09-11 15:09:16 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE ANCHOR SPACING TABLE IN THE PRODUCT APPROVAL FOR | | THE CLEAR PANELS IS ILLEGIBLE. I WAS NOT ABLE TO VERIFY | | THE ANCHOR SPACING. SUBMIT LEGIBLE PRODUCT APPROVAL. | | FBC 107.2.1 | | | | 2) THE ANCHOR SPACING IN THE SCHEDULE FOR THE ROLL UP | | DOOR OF 9" IS NOT CORRECT FOR 50 PSF, A 118" SPAN, | | TRAPPED MOUNT AND 5/16 TAPCONS. THE ANCHOR SPACING | | TABLE ON SHEET 17 HAS 5.5" FOR THIS INSTALLATION. THE | | 9" ANCHOR SPACING IS FOR 3/8" DIAMETER KWIK BOLT 3 | | ANCHORS IN THE TABLE ON SHEET 16. FBC 107.2.1 |
|