2020-11-03 13:28:42 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| ALTERNATE: CONTACT PETER VALENTI (561) 805-6673 |
| [email protected] |
| |
| 1ST REVIEW: FBC 2017 6TH EDITION |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected] AND REQUEST |
| THAT IT BE CONVERTED TO PROJECTDOX. |
| |
| 1. FBC B 107.2.1. PROVIDE DRAWING DETAIL SHOWING |
| CONSTRUCTION METHOD OF PROPOSED NEW SHOWER WALLS AND |
| SHOWING COMPLIANCE WITH R307.2 AND R702.4.2. |
| 2. FBC R 310.4. REVISE PLAN TO SHOW REQUIRED MEANS OF |
| ESCAPE. INCLUDE ROOM DESIGNATION. MUST SHOW/DESIGNATE |
| ON PLANS. SECOND REQUEST. |
| 3. SUBMITTED PRODUCT APPROVAL COVER PAGE FL11943-R3 IS |
| FOR ACCORDION SHUTTERS; SUBMITTED PRODUCT APPROVAL |
| EVALUATION REPORT AND INSTALLATION INSTRUCTIONS |
| FL11398-R4 IS FOR STORM PANELS. PROVIDE A COMPLETE SET |
| OF PRODUCT APPROVALS FOR THE CORRECT HURRICANE |
| PROTECTION SYSTEM USED. |
| 4. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF |
| PROTECTIVE DEVICES OR ASSEMBLIES: COLUMN HEADING |
| ?SHUTTER MOUNTING CONNECTION TYPE PER PRODUCT |
| APPROVAL?; PROVIDE INFORMATION FROM PRODUCT APPROVAL, |
| USE ALPHABETICAL LETTERS AND NUMBERS THAT CORRESPONDS |
| WITH THE CONNECTION TYPE FOR THE TOP AND BOTTOM |
| CONNECTIONS. |
| |