2020-10-02 12:11:36 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) CIRCLE OR HI-LIGHT THE APPROPIATE ITEMS THAT APPLY |
| TO THIS PROJECT (SUCH AS SIZE, GLASS TYPE, DESIGN |
| PRESSURE) ON THE PRODUCT APPROVALS. FBC 107 |
| |
| 2) THE CONTRACT THAT WAS SUBMITTED IS FOR ANOTHER |
| PROJECT. FBC 107.2.1 |
| |
| 3) INDICATED ON THE FLOOR PLAN THE LOCATION OF THE |
| BEDROOMS AND SHOW THE EMERGENCY ESCAPE AND RESCUE |
| OPENINGS WILL COMPLY WITH FBC EXISTING BUILDING SECTION |
| 702.5 EMERGENCY ESCAPE AND RESCUE OPENINGS. WHERE |
| WINDOWS ARE REQUIRED TO PROVIDE EMERGENCY ESCAPE AND |
| RESCUE OPENINGS IN GROUP R-2 AND R-3 OCCUPANCIES AND |
| ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES REGULATED |
| BY THE FLORIDA BUILDING CODE, RESIDENTIAL, REPLACEMENT |
| WINDOWS SHALL BE EXEMPT FROM THE REQUIREMENTS OF |
| SECTIONS 1030.2, 1030.3 AND 1030.5 OF THE FLORIDA |
| BUILDING CODE, BUILDING AND SECTIONS R310.21 AND |
| R310.2.3 OF THE FLORIDA BUILDING CODE, RESIDENTIAL |
| ACCORDINGLY, PROVIDED THE REPLACEMENT WINDOW IS THE |
| MANUFACTURER'S LARGEST STANDARD SIZE WINDOW THAT WILL |
| FIT WITHIN THE EXISTING FRAME OR EXISTING ROUGH |
| OPENING. THE REPLACEMENT WINDOW SHALL BE PERMITTED TO |
| BE OF THE SAME OPERATING STYLE AS THE EXISTING WINDOW |
| OR A STYLE THAT PROVIDES FOR AN EQUAL OR GREATER WINDOW |
| OPENING AREA THAN THE EXISTING WINDOW. |
| |