Plan Review Notes
Plan Review Notes For Permit 20080311
Permit Number 20080311
Review Stop G
Sequence Number 2
Notes
Date Text
2020-09-11 07:32:052ND REVIEW FBC-2017 MECHANICAL
 PERMIT
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) BASED ON THE LONGEST LENGTH (50?) AND TABLE 402.4(2)
 OF THE 2017 FBC FG THE 1 ?? GALVANIZED PIPING AT THE
 METER WILL NOT SUPPLY THE NEW LOAD. IT CAN ONLY SUPPLY
 583,000 BTU?S. PLEASE CORRECT THIS AND RESUBMIT.
  
 2) PLEASE ALSO INCLUDE ON THE DRAWING THE DESIGNERS
 SIGNED AND PRINTED NAME.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  