Date |
Text |
2021-04-20 21:43:30 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT-20080259 |
| 4/20/2021 |
| |
| CODES IN EFFECT: |
| |
| FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| EDITION 2020 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1- SEPARATE SEWER CONNECTION REQUIRED FOR EACH |
| APARTMENT AS PER FBC P 701.3 |
| A BUILDING HAVING PLUMBING FIXTURES INSTALLED AND |
| INTENDED FOR HUMAN HABITATION, OCCUPANCY OR USE ON |
| PREMISES ABUTTING ON A STREET, ALLEY OR EASEMENT IN |
| WHICH THERE IS A PUBLIC SEWER SHALL HAVE A SEPARATE |
| CONNECTION WITH THE SEWER. WHERE LOCATED ON THE SAME |
| LOT, MULTIPLE BUILDINGS SHALL NOT BE PROHIBITED FROM |
| CONNECTING TO A COMMON BUILDING SEWER THAT CONNECTS TO |
| THE PUBLIC SEWER. |
| |
| 2- SUBMIT A SLAB REPAIR DETAIL FOR REVIEW. SHOW THE |
| WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE |
| CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE. |
| SHOW THE SIZE AND LENGTH OF THE DOWELS, THE MINIMUM |
| EMBEDMENT DEPTH INTO THE EXISTING SLAB, AND THE SPACING |
| OF THE DOWELS ON THE CENTER. THE REPAIR SHALL ALSO |
| INCLUDE TERMITE TREATMENT OF THE SOIL AND THE REQUIRED |
| VAPOR BARRIER OVER THE SOIL. A COPY OF THE TERMITE |
| CERTIFICATE SHALL BE ONSITE FOR A FINAL INSPECTION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| ATELYO BELISLE |
| PLUMBING INSPECTOR / |
| PLUMBING PLAN REVIEW |
| AVAILABLE FROM 1:00 PM TO 4:00 PM |
| [email protected] |
| 561-805-6695 |
| |
| |