Plan Review Notes
Plan Review Notes For Permit 20080259
Permit Number 20080259
Review Stop E
Sequence Number 2
Notes
Date Text
2020-11-23 15:17:28ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
  
 CORRECTED.
  
 2.PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
  
 NOT CORRECTED. NEED TO PROVIDE LOAD CALCULATIONS FOR
 THE ENTIRE SERVICE IN ADDITION TO THE LOAD CALCULATIONS
 FOR EACH INDIVIDUAL PANEL.
  
 3.PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 PANEL SCHEDULES SHOWN ARE LABELED LP1 AND LP2 WHILE
 RISER DIAGRAM AND POWER LAYOUT SHOW THEM AS PANEL A AND
 PANEL B. PLEASE CORRECT TO INDICATE PROPER NAMES OF
 PANELS. MAIN CIRCUIT BREAKERS ARE INDICATED AS 100 AMPS
 ON RISER DIAGRAM BUT AS 125 AMPS ON PANEL SCHEDULES.
 PLEASE CORRECT. ADJUST FEEDER SIZES IF NEEDED
  
 4.ELECTRICAL PLAN IS REQUIRED TO BE SIGNED/SEALED BY A
 DESIGN PROFESSIONAL OR SIGNED BY THE ELECTRICAL
 CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 NOT CORRECTED.
  
 5.PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S).
 SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC
 107.2.1
  
 NOT CORRECTED. PLEASE SHOW CONDUCTORS SIZES FOR MAIN
 SERVICE CONDUCTORS, FEEDERS TO PANELS A AND B,
 EQUIPMENT GROUNDING CONDUCTOR SIZES, PLEASSE SPECIFY
 GROUNDING ELECTRODE CONDUCTOR SIZE, GROUNDING ELECTRODE
 SYSTEM.
  
 6.PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER
 CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
  
 PARTIALLY CORRECTED. SMOKE DETECTOR ALSO REQUIRED IN
 LIVING/SLEEPING AREA OF STUDIO (APARTMENT B).
  
 7.PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A NOTE
 WILL SUFFICE. NEC 406.12; FBC RE E4002.14
  
 CORRECTED
  