2020-08-13 11:29:56 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| ALTERNATE: CONTACT SAMANTHA HILL (561) 805-6724 |
| [email protected] |
| |
| 1ST REVIEW: FBC 2017 6TH EDITION |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected] AND REQUEST |
| THAT IT BE CONVERTED TO PROJECTDOX. |
| |
| |
| 1. FBC R 301 FAC9N-3 FOR FLORIDA STATE PRODUCT APPROVAL |
| FL1850 IS INCOMPLETE, PROVIDE THE FOLLOWING ADDITIONAL |
| INFORMATION: COVER SHEET (WWW.FLORIDABUILDING.ORG, THIS |
| WILL INCLUDE THE CODE VERSION, PRODUCT APPROVAL NUMBER, |
| STATUS, GENERAL INFORMATION ABOUT THE PRODUCT) |
| EVALUATION REPORT. PROVIDE TWO COMPLETE SETS FOR THE |
| PROPOSED ACCORDION SHUTTERS USED. |
| 2. FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION |
| OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL |
| INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL |
| SPREADSHEET): |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS?PAGE=2 |
| 3. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE |
| NOTE PAGE 13 OF 20, FACTORS APPLY DEPENDING ON |
| SUBSTRATE, EDGE DISTANCE AND FASTENER. FOR FASTENER, IF |
| USING TAPCON, BE SPECIFIC AS TO WHICH TAPCON (TAPCON |
| W/ADVANCED THREADFORM TECHNOLOGY REQUIRES A ( .9 |
| FACTOR). REDUCE ANCHOR SPACING BY MUTIPLYING SPACING |
| SHOWN ON SCHEDULE BY THE FACTOR. |
| |