2020-09-09 13:38:03PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE MULLION THAT WAS SELECTED ON SHEET 3 OF 18 ON
 NOA NO. 19-0131.11 DOES NOT MEET THE REQUIRED NEGATIVE
 PRESSURE FOR THE OPENING. THE REQUIRED PRESSURES FOR
 THE OPENING ARE +65.9 , -120.8 PSF. THE 2 X 4 STD.
 MULLION IS RATED FOR + OR - 106.2 WHICH IS MEETS THE
 POSITIVE PRESSURE BUT NOT THE NEGATIVE. THE 2 X 4
 CUSTOM MULLION HAS A + OR - 130 PSF WHICH WILL WORK.
 SELECT A MULLION THAT HAS A DESIGN PRESSURE OF MORE
 THAN 120.8 PSF.