Plan Review Notes For Permit 20080154 |
Permit Number |
20080154 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-08-19 07:30:12 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. NOA 17-0207.02 INCLUDES TWO ASSEMBLIES; THE ONE | | PROPOSED WAS NOT INDICATED. HOWEVER, C1 CANNOT BE USED | | AS THE DESIGN PRESSURE LIMITATION IS TOO LOW FOR ZONES | | 2 AND 3 AND GENERAL LIMITATION #9 IS NOTED (CANNOT | | UTILIZE ENHANCED FASTENING). | | | | SYSTEM D1 (PAGES 7-8) HAS A LIMITATION OF -67.5 FOR | | FASTENER #1, -52.5 FOR FASTENER #2. BOTH REQUIRE | | ENGINEERING, SEE GENERAL LIMITATION #7. | | | | 2. FBC 107, PRODUCT APPROVALS ARE TO BE REVIEWED BY | | DESIGNER OF RECORD. | | | | 3. SCOPE NOT CLEAR; THE APPLICATION STATES THIS IS A | | REROOF. THE MASTER PERMIT WAS FOR PORTE COCHERE | | REPLACEMENT. DOES THIS APPLICATION INCLUDE WORK IN | | ADDITION TO THE PORTE COCHERE? IF YES, PROVIDE VALUE | | THAT WAS NOT INCLUDED IN THE MASTER PERMIT, FBC 109. | | | | |
|