2020-08-19 07:30:12****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. NOA 17-0207.02 INCLUDES TWO ASSEMBLIES; THE ONE
 PROPOSED WAS NOT INDICATED. HOWEVER, C1 CANNOT BE USED
 AS THE DESIGN PRESSURE LIMITATION IS TOO LOW FOR ZONES
 2 AND 3 AND GENERAL LIMITATION #9 IS NOTED (CANNOT
 UTILIZE ENHANCED FASTENING).
  
 SYSTEM D1 (PAGES 7-8) HAS A LIMITATION OF -67.5 FOR
 FASTENER #1, -52.5 FOR FASTENER #2. BOTH REQUIRE
 ENGINEERING, SEE GENERAL LIMITATION #7.
  
 2. FBC 107, PRODUCT APPROVALS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD.
  
 3. SCOPE NOT CLEAR; THE APPLICATION STATES THIS IS A
 REROOF. THE MASTER PERMIT WAS FOR PORTE COCHERE
 REPLACEMENT. DOES THIS APPLICATION INCLUDE WORK IN
 ADDITION TO THE PORTE COCHERE? IF YES, PROVIDE VALUE
 THAT WAS NOT INCLUDED IN THE MASTER PERMIT, FBC 109.
  
  