2020-08-05 10:15:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO SCOPE OF WORK SUBMITTED.
  
 PLEASE PROVIDE A DETAILED SCOPE OF WORK.
  
  
  
 2) THE APPLICATION INDICATES A CHANGE OF ANNUCIATOR;
 HOWEVER, THE PLAN SHEET APPEARS TO SHOW SD THAT ARE
 CIRCLED AND NO INDICATION OF AN
 ANNUNCIATOR/ANNUNCIATION EQUIPMENT.
  
 PLEASE REVIEW AND CONFIRM THE SCOPE OF WORK AND
 ACCURATELY RELFECT IT ON THE PLAN SHEET.
  
  
  
 2A) PLEASE PROVIDE EXISTING LOCATIONS AND NEW LOCATIONS
  
 PROVIDE DETAILS.
  
  
  
 2B) IS ANY OF THE PROPOESD WORK INVLOVE NEW EQUIPMENT
 AND WIRING OR MOVING EXISTING?
  
 PLEASE PROVIDE A STATEMENT AND PROVIDE EQUIPMENT
 SPECIFICATION SHEETS.
  
  
  
 3) IS ANY OF THE PROPOSED WORK TIED INTO THE THE ANY
 EXISTING FIRE ALARM SYSTEM/EQUIPMET.
  
 PLEASE PROVIDE A STATEMENT
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL