Plan Review Notes For Permit 20071492 |
Permit Number |
20071492 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-08-17 16:10:08 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | IS ADEQUATE. NEC 215.2, 220, 408.30; | | | | 2) PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | CIRCUITS 210.8, 210.12, 215.5, 408.4 | | | | 3) PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | NEC 110.9, 110.10 | | | | 4) SOME AREAS LOOK TO BE WET LOCATIONS ALL RECEPTACLE | | OULETS TO BE GFCI PROTECTED PER 210.8 | | | | 5) PROVIDE A NOTE TO INDICATE COMPLIANCE WITH FBC CE | | 405.2 AUTOMATIC LIGHTING CONTROL AND LIGHTING DENSITIES | | PER CODE SECTION. |
|