Plan Review Notes
Plan Review Notes For Permit 20071441
Permit Number 20071441
Review Stop P
Sequence Number 2
Notes
Date Text
2020-08-20 15:26:25STRUCTURE IS BUILT IN 1925. PERMIT RECORDS ONLY GO BACK
 TO 2006 AND CONTAIN NO REFERENCE TO EXISTING GAS PIPE
 NOR IS THERE ANY RECORD OF THE IN HOME APPLIANCES SUCH
 AS THE RANGE, DRYER, TANKLESS WATER HEATER. FLORIDA
 PUBLIC UTILITIES RECORDS SHOW THAT THE GAS WAS TURNED
 ON IN 2006 AND THE METER WAS EXISTING AT THAT TIME.
 ADDITIONALLY IT IS NOT KNOWN WHETHER OR NOT THE
 EXISTING TANKLESS WATER HEATER REPLACED AN EXISTING GAS
 OR ELECTRIC WATER HEATER IN ANOTHER LOCATION. AT THE
 PLUMBING INSPECTOR'S DISCRETION, SHOW THAT ANY EXISTING
 GAS SYSTEM INFRASTRUCTURE AND PLUMBING WATER PIPE TO
 THE TANKLESS WATER HEATER, INCLUSIVE OF PIPING AND
 APPLIANCES, IS CODE COMPLIANT. THIS MAY REQUIRE
 PROVIDING DOCUMENTATION OF, OPENING OF WALLS AND
 FLOORS, PRESSURE TESTS, ETC., AS DETERMINED BY THE
 PLUMBING INSPECTOR. PLEASE CALL TIM LARGE AT
 561-805-6692 FOR ADDITIONAL INFORMATION AND/OR
 CLARIFICATION.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved