Plan Review Notes
Plan Review Notes For Permit 20071441
Permit Number 20071441
Review Stop G
Sequence Number 2
Notes
Date Text
2020-08-20 15:24:5020071441 525 SUNSET RD
  
 GAS COMMENTS: APPROVED
  
 CITY OF WEST PALM BEACH GAS PIPING AFFIDAVIT OR
 MANOMETER TEST DOCUMENT REQUIRED AT JOBSITE FOR FINAL
 GAS INSPECTION. CALL 561-805-6692 FOR FURTHER
 INFORMATION.
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 PROVIDE PAPER BACKUP WITH PRINTED NAME "MARK GIMMLER"
 AS WELL AS SIGNATURE TO THE BUILDING DEPARTMENT.
  
 PROVISO:
 STRUCTURE IS BUILT IN 1925. PERMIT RECORDS ONLY GO BACK
 TO 2006 AND CONTAIN NO REFERENCE TO EXISTING GAS PIPE
 NOR IS THERE ANY RECORD OF THE IN HOME APPLIANCES SUCH
 AS THE RANGE, DRYER, TANKLESS WATER HEATER. FLORIDA
 PUBLIC UTILITIES RECORDS SHOW THAT THE GAS WAS TURNED
 ON IN 2006 AND THE METER WAS EXISTING AT THAT TIME.
 ADDITIONALLY IT IS NOT KNOWN WHETHER OR NOT THE
 EXISTING TANKLESS WATER HEATER REPLACED AN EXISTING GAS
 OR ELECTRIC WATER HEATER IN ANOTHER LOCATION. AT THE
 PLUMBING INSPECTOR'S DISCRETION, SHOW THAT ANY EXISTING
 GAS SYSTEM INFRASTRUCTURE AND PLUMBING WATER PIPE TO
 THE TANKLESS WATER HEATER, INCLUSIVE OF PIPING AND
 APPLIANCES, IS CODE COMPLIANT. THIS MAY REQUIRE
 PROVIDING DOCUMENTATION OF, OPENING OF WALLS AND
 FLOORS, PRESSURE TESTS, ETC., AS DETERMINED BY THE
 PLUMBING INSPECTOR. PLEASE CALL TIM LARGE AT
 561-805-6692 FOR ADDITIONAL INFORMATION AND/OR
 CLARIFICATION.
  
 THE MANUFACTURER?S SPECIFICATION/INSTALLATION MANUAL
 FOR POOL HEATER SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FBC FG 305.1.
  
 REGULATORS INSTALLED OUTDOORS SHALL BE INSTALLED IN A
 POSITION THAT PREVENTS MOISTURE (RAIN, SNOW) AND
 FOREIGN PARTICLES FROM ENTERING THE VENT AS REQUIRED BY
 THE MANUFACTURER?S START UP MANUAL TDC-0851-001
 REGULATOR: B-SERIES INSTALLATION
  
 FBC FG TABLES FOR 2PSI AND LOW PRESSURE GALVANIZED
 PIPING AS WELL AS THE SUBMITTED TABLE 402.4 (22) FOR
 2PSI PE PIPING SHALL BE ONSITE AT THE TIME OF
 INSPECTION
  
 PROVIDE TRACER WIRE FOR PE PIPING PER FBC FG 404.17.3.
 SIZE SHALL BE NOT LESS THAN 18 AWG AND THE INSULATION
 TYPE SHALL BE SUITABLE FOR DIRECT BURIAL.
  
 PE PIPING SHALL NOT PASS UNDER BUILDING PER
 FBC.404.17.1.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  