Plan Review Notes
Plan Review Notes For Permit 20071441
Permit Number 20071441
Review Stop G
Sequence Number 1
Notes
Date Text
2020-08-10 11:55:001ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20071441
  
 CODES IN EFFECT:
  
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) APPLICATION GIVES AN ADDRESS OF 525 SUNSET RD, THE
 ISOMETRIC DRAWING GIVES AN ADDRESS OF 818 AVON RD.
 PLEASE GIVE THE CORRECT ADDRESS ON BOTH FORMS. FBC FS
 107.2.1
  
 2) PLEASE PROVIDE A DETAILED SCOPE OF WORK: APPLICATION
 STATES ?INSTALLING NATURAL GAS LINE TO CUSTOMER
 APPLIANCES? THE SUBMITTED PACKET SHOWS SPECS. FOR
 SEVERAL APPLIANCES BUT THE ISOMETRIC SHOWS A LINE FOR
 EXISTING APPLIANCES AND A NEW LINE ATTACHING AT METER
 AND RUNNING TO A NEW POOL HEATER. THIS IS CONFUSING, IS
 THIS A NEW GAS LINE FOR THE ENTIRE SYSTEM? IS THIS AN
 EXISTING GAS LINE THAT YOU ARE ATTACHING A NEW GAS LINE
 FOR THE POOL HEATER? IS THERE EXISTING GAS LINES AT
 THIS HOME AND YOU ARE CHANGING OUT ALL THE APPLIANCES
 FOR NEW ONES? PLEASE SHOW THE EXISTING GAS LINE WITH
 ALL APPLIANCES ATTACHED TO IT ALONG WITH THE TOTAL
 LONGEST LENGTH TO THE MOST REMOTE APPLIANCE FROM THE
 METER. FBC FS 107.2.1
  
 3) DESIGNER OF SYSTEM MUST PRINT AND SIGN HIS COMPLETE
 NAME, NOT JUST INITIALS, ON THE ISOMETRIC DRAWING. FBC
 FS 107.2.1
  
 4) IS THE EXISTING GAS PIPING SYSTEM A 2 PSI SYSTEM?
 FBC FS 107.2.1
  
 5) PLEASE PROVIDE THE SPECS FOR THE REGULATOR USED. FBC
 FS 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  